LonTalk

®

option

Chiller Controller 8040

Mandatory network variables

Optional network variables

nv1

nviChillerEnable
snvt_switch

nv2

nv7

nv8

nv3

nv4

nv11

nv12

nv13

nv15

nv16

nviCoolSetpt
snvt_temp_p

nviMode
Snvt_hvac_mode

nviHeatSetpt
snvt_temp_p

nvoOnOff
snvt_switch

nvoActiveSetpt
snvt_temp_p

nvoLvgCHWTTemp
snvt_temp_p

nvoEntCHWTTemp
snvt_temp_p

nvoEntCndWTemp
snvt_temp_p

nvoAlarmDescr
snvt_str_asc

nvoChillerStat
snvt_chlr_status

Note: BAS intergrators requiring .xif file need to contact their local sales
representative.
Other optional network variables are not supported.

Object details

Figure 10

LED meaning and function

Green Status LED
LED status

Meaning/Function

LED is OFF continuously.

• Normal condition
• Broken hardware
• No power

LED is ON.

• Broken hardware

·

• During the activation of the service pin
• The node is Applicationless

LED blinks 1second then always OFF

• When receiving a WINK command from the network (1)

LED blinks ½ second ON then always OFF

• Normal operation (usually after a reset)

LED flashes once every second

• The node card is not configured
• The node card is in continuous reset

(1) By sending a request, you can request the controller’s green status LED to blink (“wink”), a notification that the controller received the signal and is

communicating.

Red Service LED
LED status

Meaning/Function

LED is ON for 20 seconds when power is applied to the controller

• The controller is in a reset phase

LED is OFF continuously

• The controller is operating normally
• Broken hardware

LED is ON during 2 seconds then always OFF

• When power is applied to the controller
• After a reset

LED is ON continuously

• The controller is not working properly
• Broken hardware
• Problems of connection with the CH532 module

26

CG-SV01B-E4

Advertising