Unit configuration menu: “configuration – American Standard TRACER CH532 User Manual

Page 20

Advertising
background image

6. Sensors and transducers
To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

Temp probe: Sensor type:

NTC (factory setting)
PT100

Press probe: Pressure transducer:

0..10V
0..1V
0..20mA
4..20mA
(factory setting)

Min Press: Pressure at 0V, 0mA or
4 mA (-1.0 to 0.0 bar - factory
setting: 0.0 bar)
Max Press: Pressure at 10V, 1V or
20 mA (16 to 50 bar - factory
setting: 30bar)

7. Operation limits
To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

LP (Sat Temp): Low evaporating
pressure limit (-25 to 0°C - factory
setting: -4°C)
Timer LP: Low pressure fault timer
after compressor start (0 to 300 s -
factory setting: 60s)
HP Cool StP: High pressure limit in
cooling mode (15 to 40 bar - factory
setting: 28 bar)
HP Heat StP: High pressure limit in
heating mode (15 to 40 bar - factory
setting: 28 bar)

8. Analog Output (for speed inverter)
Note:
This screen is displayed only if
“Invert” has been selected in the HP
control menu (refer to §3)
To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

Low 0V: Minimum fan speed (0
to 10 bar - factory setting: 8 bar)
High 10V: Maximum fan speed
(11 to 40 bar - factory setting: 16 bar)

Temp probe

NTC

Press probe

4..20mA

Min Press

0.0bar

Max Press

30.0bar

LP (Sat Temp)

-4°C

Timer LP

60 s

HP Cool Stp

28.0 bar

HP Heat Stp

28.0 bar

Analog output

Low

OV

08.0 bar

High

10V

16.0 bar

Unit configuration menu:
“Configuration”

20

CG-SV01B-E4