9. Operating limits (cooling)

Low ambient temperature
limitation:

On: (factory setting) Low
ambiant limited
Off: Low ambient
temperature not limited

Low ambient limit: -20 to 20°C:
factory setting -10°C
Chilled water high limitation:

On: High water temperature
limited (factory setting)
Off: High water temperature
not limited

Chilled water high limit: 10 to 20 °C:
Factory setting 15°C

10. Defrost demand setpoint

Low ambient heating: -20 to 20°C,
factory setting -10°C
Setpoint at minimum ambient: 1 to
30°C, (factory setting 10°C)
Maximum ambient: -20 to 20°C:
(factory setting 12°C)
Setpoint at maximum ambient: 1 to
30°C, (factory setting 22°C)

11. Defrost cycle termination
To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

Term StP: Defrost termination
setpoint (10 to 30bar - factory
setting: 20 bar)
Drying time: Drying time (5 to 30
seconds - factory setting: 12s)
Max Defrost: Maximum defrost time
(5 to 30 minutes - factory setting:
7 min)
Min cycle: Minimum time between
defrost cycle (15 to 60min - factory
setting: 25 min)

Note: Dual circuits have two
independent refrigerant circuits.
Defrost cycle will only occur on the
circuit that needs it. The other circuit
will continue its normal operation if
required.

12. Compressor alarm
To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

Compressor alarm: Operating hours
for a warning (0 to 999000 hours by
1000 hours)

Setting compressor alarm at
000000 h will disable the
function.

Note: Total operating hours =
compressor running hours + 3 x
compressor starts
Default parameters?: Set the default
parameters
Y: Reset all parameters
N: Keep all parameters

Note: When resetting, all parameters
programmed on site will be
definitively lost. Only factory default
set parameters will be kept. Full
configuration of the unit will have to
be checked.

Low Amb Cooling

On

Low Amb Limit

-10.0°C

CW High Limit

On

CW High Limit

15.0°C

Term Stp

20.0 bar

Drying time

12 s

Max Defrost

7 min

Min cycle

25 min

Compressor alarm

00000 h

Default parameters?

N

Unit configuration menu:
“Configuration”

CG-SV01B-E4

21

Low Amb Heat

-10.0°C

StP Min Temp

10.0°C

Defrost Max

12.0°C

StP Max Temp

22.0°C