Alto-Shaam FRYTECH ASF-60G series User Manual

Page 11

Advertising
background image

Use an approved
gas pipe sealant at
all external threaded
connections, gas
piping used on gas
connections must
avoid sharp bends
that may restrict the
flow of gas to the
appliance. If the
connected pressure
exceeds 14.0” W.C. (3.5 kPa), a step-down regulator is
required to be supplied by the owner/operator.

Close the individual manual shut-off valve to
isolate the fryer from the gas supply piping system
during any pressure testing at test pressures equal
to or less than

1/2

psig. (3.4 kPa). The fryer and

individual shut-off valve must be disconnected

from the gas supply piping system during

any pressure testing at pressures in

excess of 1/2 psig. (3,4 kPa).

In the U.S.A., installation must conform to local
codes or, in the absence of local codes, with the
current edition of the National Fuel Gas Code,
NFPA-54 and ANSI Z83.11a CSA 1.8a 2004 (or
latest edition). In Canada, installation must be in
accordance with local codes, CAN/CGA-B149.1,
Installation for Natural Gas Burning Appliances
and Equipment
(latest edition) or CAN/
CGA-B149.2 Installation for Propane Burning
Appliances and Equipment
(latest edition).

The inlet supply line must be properly sized
to accommodate all individual appliances
simultaneously used on the same line but must
never be smaller than 3/4

I.D.

LEAK TESTING

Installation requires gas leak testing on all gas
piping and fittings. Use an approved electronic
leak device or a soap and water solution at all gas
connections. If bubbling appears when using a soap
and water solution, the connection must be refitted.
Never use an open flame to leak test.

INCORRECT

CORRECT

A
B

C

D

E

F

G

H

GAS INTAKE

A-G Installation elbow

B Wall Valve

C-D Three-piece union fitting

(minimum 1 per installation)

E-F End connector for the flexible tube

H Marking line

G A S C O N N E C T I O N

D A N G E R

Installation, air adjustment and/or
service work must be in accordance
with all local codes and must be
performed by a certifi ed service
technician qualifi ed to work on
gas appliances.

D A N G E R

NEVER USE AN OPEN

FLAME TO LEAK TEST.

I N S T A L L A T I O N

Gas Fryer Operation & Care Manual • 9