Applying power, 1 connecting to earth ground, Hapter – Beijer Electronics QTERM®-A12 User Manual

Page 11: Pplying, Ower

Advertising
background image

QTERM-A12 Terminal

5

C

HAPTER

3

A

PPLYING

P

OWER

Power is supplied to the QTERM-A12 terminal via the COM1 serial port connector or the
3-pin power terminal strip for input power, return and chassis ground. The QTERM-A12 may
also be equipped with an optional Power-over-Ethernet (PoE) interface. When powered by the
3-pin power terminal strip or the COM1 serial port, the QTERM-A12 has a 10- to 32-volt DC
input range and can be powered directly from a 12- or 24-volt DC power supply (the current
will vary depending on the input voltage; see table below).

3.1 Connecting to Earth Ground

N

OTE

The chassis ground connection of the QTERM-A12 is electrically connected to the exposed
conductive parts of the QTERM-A12 for safety purposes. The chassis ground connection
MUST be connected to an external protective earthing system.

The QTERM-A12 has a chassis ground terminal and a chassis ground connection on the 3-pin
power terminal strip on the back of the terminal. (See

Figure 6 on page 24

and

Figure 15 on

page 29

for the location of the chassis ground terminal and the 3-pin power terminal strip.) The

terminal should be connected to earth ground (protective earth). The chassis ground is not con-
nected to signal common of the terminal. Maintaining isolation between earth ground and
signal common is not required to operate the terminal; however, other equipment connected to
the terminal may require isolation between signal common and earth ground. To maintain iso-

C

AUTION

For Class I, Division 2 installations:
Do not connect or disconnect cables while power is applied unless the area is known to be
non-hazardous.

Power Consumption

Terminal

12 VDC

24 VDC

PoE (48 VDC)

Standby

1

1. Standby power consumption is measured when the display has been powered down and the
operating system has entered system idle mode.

1.3 W

1.6 W

3.0 W

Typical

2

2. Typical power consumption is measured when the display is at full brightness and a polygon
drawing application is running.

8.5 W

9.1 W

10.5 W

Estimated Maximum

3

3. Estimated maximum power consumption is measured with serial, USB and Ethernet commu-
nications active. In addition, several applications are running including video with full volume
and two USB mass storage loads are being powered.

12.1 W

13.1 W

14.2 W

Advertising