Modbus ramp control time – Beijer Electronics AN-BEI-E2-038 User Manual

Page 3

Advertising
background image

APPLICATION NOTE AN‐BEI‐E2‐038 

Date: 15/02/12 

 

AN‐BEI‐E2‐038 Modbus RTU Control and Register Mapping 

 

Memory Map: 

Table 1: Control and status registers 
Note : All registers are Holding Registers 

 

Register 
Number 

Parameter 
Number 

Upper byte 

Lower Byte

Format

Min

Max

Command 

Type 

Scaling

1* 

‐ 

Control Word

WORD

0

15

03,06

R/W 

See Below

2* 

‐ 

Frequency Setpoint 

S16

0

5000

03,06

R/W 

1dp, e.g. 100 = 10.0Hz

3* 

‐ 

Reserved 

03,06

R/W 

 

4* 

‐ 

Modbus ramp control time 

U16

0

60000

03,06

R/W 

2dp, e.g. 500 = 5.00s

‐ 

Reserved 

03

 

6* 

‐ 

Error code 

Drive status

03

See Below

7* 

‐ 

Output Frequency 

S16

0

5000

03

1dp, e.g. 100 = 10.0Hz

8* 

‐ 

Motor Current

U16

0

03

1dp, e.g. 100 = 10.0A

9* 

‐ 

Reserved 

03

 

10 

‐ 

Reserved 

03

 

11 

P00‐04 

Digital Input Status 

WORD

0000

1111

03

See Below

12 

P00‐20 

Rating ID 

U16

03

Internal Value

13 

P00‐20 

Power rating

U16

03

2dp, e.g. 37 = 0.37kW / HP

14 

P00‐20 

Voltage rating

U16

03

Supply Voltage

15 

P00‐18 

IO processor software version 

U16

03

2dp, e.g. 103 = 1.03

16 

P00‐18 

Motor control processor software version

U16

03

2dp, e.g. 103 = 1.03

17 

P00‐20 

Drive type 

U16

03

Internal Code

18 

‐ 

Reserved 

03

 

19 

‐ 

Reserved 

03

 

20 

P00‐01 

Analog 1 input result 

U16

0

1000

03

1dp, e.g. 500 = 50.0%

21 

P00‐02 

Analog 2 input result 

U16

0

1000

03

1dp, e.g. 500 = 50.0%

22 

P00‐03 

Speed reference value 

S16

0

5000

03

1dp, e.g. 500 = 50.0Hz

23 

P00‐08 

DC bus voltages 

U16

0

1000

03

600 = 600 Volts

24 

P00‐09 

Drive temperature 

S16

‐10

150

03

50 = 50°C

25 to 30 

‐ 

Reserved 

03

 

* When using the external fieldbus gateways (PROFIBUS, DEVICENET, ETHERNET) these registers are available. 
Format 
WORD = WORD Format, functions assigned to individual bits 
S16 = Signed 16 Bit Integer 
U16 = Unsigned 16 bit Integer 

 

 

Advertising