Beijer Electronics AN-BEI-E2-038 User Manual

Page 9

Advertising
background image

APPLICATION NOTE AN‐BEI‐E2‐038 

Date: 15/02/12 

 

AN‐BEI‐E2‐038 Modbus RTU Control and Register Mapping 

 

Analog and Digital Input Configurations when in MODBUS control mode (P12 = 3 or 4)   

By changing the value in P‐15 adjusts the functionality of the control terminals as below: 
 

P‐15 

Digital input 1 (T2) 

Digital input 2 (T3) 

Digital input 3 (T4)

Analog input (T6)

Comments

0..2, 
4..5, 
8..12 

Open: Stop (disable) 
Closed: Run (enable) 

No effect 

No effect 

No effect 

Run and stop commands 
given via the RS485 link and 
Digital input 1 must be 
closed for the drive to run.  

1)

 

Open: Stop (disable) 
Closed: Run (enable) 

Open : Master speed ref 
Closed : Preset speed 1 

External trip input : 
Open: Trip, Closed: Run 

No effect 

Connect external thermistor 
type PT100 or similar to  
digital input 3  

1)

 

Open: Stop (disable) 
Closed: Run (enable) 

Open : Master speed ref
Closed : Analog input 

External trip input :
Open: Trip, Closed: Run 

Analog input reference 

Master Speed Ref ‐ start and 
stop controlled via RS485. 
Keypad Speed Ref ‐ drive 
auto runs if digital input 1 
closed, depending on P‐31 
setting 

1)

 

Open: Stop (disable) 
Closed: Run (enable) 

Open : Master speed ref 
Closed : keypad speed ref 

External trip input : 
Open: Trip, Closed: Run 

No effect 

 
 
Example Wiring 

 

AUTO – MODBUS Speed 
HAND – Preset Speed 1 

AUTO – MODBUS Speed
HAND  ‐ Analog Speed ref 
(potentiometer) 

AUTO – MODBUS Speed 
HAND – Keypad Speed ref (UP & DOWN 
keys on drive) 

 

 

 

 

 

Advertising