Beijer Electronics AN-BEI-E2-038 User Manual

Page 8

Advertising
background image

APPLICATION NOTE AN‐BEI‐E2‐038 

Date: 15/02/12 

 

AN‐BEI‐E2‐038 Modbus RTU Control and Register Mapping 

 

Modbus Exception Response Telegrams 

Under some circumstances, the drive may reply with an Exception Response (error) in response to a request telegram sent from 
the network master, for example where the master tries to read a register which does not exist. Exception Responses which can 
be generated by the drive are listed below:‐  
 
Exception Code 1: Invalid Request 
Returned under the following conditions 

• Network Master sends an unsupported Modbus command (e.g. Read Coils). 
• Run command issued to drive whilst the drive is not set for Modbus Control Mode (e.g. P1‐12 <>4). 
• Run command issued to drives whilst the drive is not enabled (e.g. Digital Input 1 is open). 
• Run command issued to drive whilst the drive is in a tripped condition. 

 
Exception Code 2: Invalid Modbus register 
Returned under the following conditions 

• Network Master attempts to read or write a register that does not exist within the drive. 

 
Exception Code 3: Register Value Out of Range 
Returned under the following conditions 

• Network Master attempts to write a holding register with a value outside the range of the register 

 
Exception Code 6: Drive Busy 
Returned under the following conditions 

• Drive busy due to internal data transfer. The Network Master should re‐send the message after a delay 

 
 

Dataflow example: 

Read data from register 6:

 
Request:    [01]                     [03]                      [00] [05]           

[00] [01]                       [94] [0B] 

   

     (Drive Addr)      (Command)         (Reg start addr)       (No. of Registers)       (Checksum) 

 
Reply:        [01]                     [03]                      [02]                   

   [00] [00]                    [B8] [44] 

   

     (Drive Addr)      (Command)         (No of data bytes)       (Data)                      (Checksum) 

 
Note: The actual start address of register 6 is 5. All data in [ ] is in 8bits Hex format. 
 
Write start command to the register 1 (suppose P‐12 = 3, P‐15 =0 and digital input 1 is closed): 
 
Request:    [01]                     [06]                      [00] [00]           

[00] [01]                       [48] [0A] 

   

     (Drive Addr)      (Command)         (Reg addr)             (Data value)                 (Checksum) 

 
Reply:        [01]                     [06]                      [00] [00]           

[00] [01]                       [48] [0A] 

   

     (Drive Addr)      (Command)         (Reg addr)             (Data value)                 (Checksum) 

 
Note: The actual address of register 1 on the data link is 0. All data in [ ] is in 8bits Hex format. 
          Reply can be error message depending on drive parameter settings and digital input status. 
 
 