Beijer Electronics AN-BEI-E2-038 User Manual

Page 4

Advertising
background image

APPLICATION NOTE AN‐BEI‐E2‐038 

Date: 15/02/12 

 

AN‐BEI‐E2‐038 Modbus RTU Control and Register Mapping 

 

Control and Status Register Descriptions: 

Read and write registers 
Register 1: Drive command 

15 

14 

13 

12 

11 

10 

7

6

5

4

3

2

High byte 

Low byte

 
Bit 0: 

Run/Stop command: Set to 1 to enable the drive. Set to 0 to stop the drive. 

 

 

Bit 1:  

Fast stop request. Set to 1 to enable drive to stop with 2

nd

 deceleration ramp. 

Bit 2: 

Reset request. Set to 1 in order to reset the drive if drive is under trip condition.  

User must clear this bit when drive is under normal condition to prevent un‐expected reset. 
Bit 3: 

Coast stop request. Set to 1 to issue a coast stop command. 

 

For  normal  operation,  Bit  3  has  the  highest  priority,  bit  0  has  the  lowest  priority  (bit  3>bit  1>bit  0).  For  example  if  user  set 
command as 0x0009, drive will do a coast stop rather than run. For normal run/start, just set this register to 1. 
 
Note  that  stat/stop(bit  0),  fast  stop(bit  1)  and  coast  stop(bit  3)  only  works  if  P‐31=  0  or  1.  Otherwise,  start/stop  function  is 
controlled by drive control terminals.  Reset function(bit  2) works all the time as long as drive is operated under Modbus control 
mode (P‐12=3 or 4). 
 

Register 2: speed reference setup 

This  register  holds  the  speed  reference  value  with  one  decimal  place  (200  =  20.0Hz).  The  maximum  speed  reference  value  is 
limited by P‐01. 
 

Register 4: Acc/Dec ramp setup 

This  register  specifies  the  drive  acceleration  and  deceleration  ramp  time.  The  same  value  is  applied  simultaneously  to  the 
acceleration and deceleration ramp times. This register is only active when P‐12 = 4. 
 

Read only registers 
Register 6: Drive status and error code 

High byte gives drive error code. (Valid when drive tripped, see appendix for details) 
Low byte gives drive status  

(0: drive stopped, 1: drive running, 2: drive tipped) 

 

Register 7: Motor speed information 

This register gives motor speed information. The data is in Hz and with one decimal place ( i.e. 234 = 23.4Hz) 
 

Register 8: Motor current 

This register gives motor current information. The data is in Amp with one decimal place (i.e. 87 = 8.7A) 
 

Register 11: Digital input status 

The value in this register represents the drive terminal digital input status (Digital input 1 to 4). Lowest bit indicates digital input 
1 status.  
 

 