APPLICATION NOTE AN‐BEI‐E2‐038 

Date: 15/02/12 

 

AN‐BEI‐E2‐038 Modbus RTU Control and Register Mapping 

 

Table 2: Parameter registers 
All  user  adjustable  parameters  within  the  drive  are  accessible  by  Modbus,  and  can  be  Read  or  Written  to.  For  further 
information regarding the parameter functions and specific settings, please refer to the User Guide. 
 

Register 

Parameter 

Description 

Format

Min

Max

Data format 

129 

01 

Max speed limit

U16

0

5*P‐09

Internal value (3000 = 50.0Hz)

130 

02 

Min speed limit

U16

0

P‐01

Internal value (3000 = 50.0Hz)

131 

03 

Accel ramp time

U16

0

60000

2dp, e.g. 300=3.00s 

132 

04 

Decel ramp time

U16

0

60000

2dp, e.g. 300=3.00s 

133 

05 

Stop mode select 

U16

0

2

0: Ramp to stop 
1: Coast to stop 
2: Ramp to stop 

134 

06 

Energy save 

U16

0

1

0: Disabled 
1: Enabled 

135 

07 

Motor rated voltage 

U16

0

250
500 

 

136 

08 

Motor rated current 

U16

0

Drive Rating Dependent

1dp, e.g. 100 = 10.0A 

137 

09 

Motor rated frequency 

U16

25

500

Data unit is in Hz 

138 

10 

Motor rated speed 

U16

0

30000

Maximum value equals to the sync speed of a 
typical 2‐pole motor 

139

 

11 

Boost voltage value 

U16

0

Size 1 ‐ 0 to 200
Size 2 ‐ 0 to 150 
Size 3 ‐ 0 to 100 

1dp, e.g. 100 = 10.0%  

140 

12 

Control mode 

U16

0

6

0: Terminal Control 
1: Keypad forward only 
2: Keypad forward and reverse 
3: Modbus control mode 
4: Modbus control with ramp control 
5 : PID control 
6 : PID control with analog speed sum 

141 

13 

Trip log 

U16

See Appendix for Details

142 

14 

Access code 

U16

0

9999

143 

15 

Digital input function 

U16

0

12

See user guide for function details 

144 

16 

Analog input format 

U16

0

6

0: 0…10V 
1: b 0…10V 
2: 0…20mA 
3: t 4…20mA 
4: r 4…20mA 
5: t 20…4mA 
6: r 20…4mA 

145 

17 

Effective switching frequency 

U16

0

5
(Drive Rating Dependent) 

0 = 4KHz 
1 = 8KHz 
2 = 12Khz 
3 =16KHz 
4 = 24KHz 
5 = 32KHz 

146 

18 

Relay output function 

U16

0

7

See user guide for function details 

147 

19 

Digital output limit 

U16

0

1000

100 = 10.0% 

148 

20 

Preset speed 1 

U16

‐P‐01

P‐01

Internal value (3000 = 50.0Hz)

149 

21 

Preset speed 2 

U16

‐P‐01

P‐01

Internal value (3000 = 50.0Hz)

150 

22 

Preset speed 3 

U16

‐P‐01

P‐01

Internal value (3000 = 50.0Hz)

151 

23 

Preset speed 4 

U16

‐P‐01

P‐01

Internal value (3000 = 50.0Hz)

152 

24 

2

nd

 deceleration ramp 

U16

0

2500

250 = 2.50s 

153 

25 

Analog output function 

U16

0

9

See user guide for function details

154 

26 

Skip frequency  

U16

0

P‐01

Internal value (3000 = 50.0Hz)

155 

27 

Skip freq band  

U16

0

P‐01

Internal value (3000 = 50.0Hz)

156 

28 

V/F adjust voltage

U16

0

P‐07

100 = 100V 

157 

29 

V/F adjust frequency 

U16

0

P‐09

50 = 50Hz 

158 

30 

Start mode select 

U16

0

6

0: Edgr‐r 
1: Auto_0 
2…6: Auto_1 to Auto_5 

159 

31 

Keypad restart mode 

U16

0

3

See user guide for details 

160 

32 

DC injection enable 

U16

0

250

250= 25.0s 

161 

33 

Spin start enable

U16

0

1

162 

34 

Brake circuit enable 

U16

0

2

See user guide for function details

163 

35 

Analog input scaling 

U16

0

5000

100 = 10% 

164 

36 

Drive address (Low byte) 

 

0

63

Drive comms address 