APPLICATION NOTE AN‐BEI‐E2‐038 

Date: 15/02/12 

 

AN‐BEI‐E2‐038 Modbus RTU Control and Register Mapping 

 

Register 12: Rating ID 

This register gives the following information: 
Drive size, drive type, Power units and Power value decimal places  

Register value (16 bits HEX format): 

 

 

 

 

 

Power Units 

0

kW

 

 

 

 

 

 

1

HP

 

 

 

 

 

Drive Type 

4

E2

 

 

 

 

 

Power Decimal Places 

0

No Decimal Places

 

 

 

 

 

 

1

One Decimal Place

 

 

 

 

 

 

2

Two Decimal Places

 

 

 

 

 

Drive Frame Size 

1

Frame Size 1

 

 

 

 

 

 

2

Frame Size 2

 

 

 

 

 

 

3

Frame Size 3

NOTE

 : Power decimal places is used for register 13 (Power rating). For example, if we have value x1x0h in register 12 and value 

15 in register 13, this gives the drive power as 1.5KW. If we have value x0x0h in register 12 and same value 15 in register 13, this 
gives drive power as 15KW. Or if we have x1x1h in register 12 and 5 in register 13, then the drive power rating is 0.5HP. If we 
have x0x1h in register 12 and 5 in register 13, this gives drive power rating as 5HP. 

 

Register 13: Power rating 

Combined with the value in register 12, this gives the drive power rating information  
 

Register 14: Voltage level 

This register gives the rated input voltage for the drive.  

i.e. 230 : 230V 

   400: 400V 

460: 460V 

 

Register 15: Software version 

This register contains the drive software version info. Value includes two decimal places. 
i.e. 103 means version 1.03 