Trouble shooting, How to diagnose by led indicator, Fnio s-series – Beijer Electronics NA-9379 User Manual

Page 56

Advertising
background image

56

MODBUS Programmable I/O NA-9379

FnIO S-Series



Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr

8. Trouble Shooting

8.1. How to diagnose by LED indicator

LED Status

Cause

Action

All LED turns off

- No power

- Check main power Cable

- System power is not supplied.

- Contact Sales team and send module
for repair.

MOD LED flashes green

- Failure of initialization EEPROM
parameter.

- Contact Sales team and send module
for repair.

MOD LED flashes red

- Excess of expansion slot
- Excess of IO size
- Wrong IO composition
- Occurrence of EEPROM checksum
error

- Use expansion slot up to 32.
- Compose that IO total size is not
excess.
- Check composition I/O Module

MOD LED is red

- Wrong address ID
- Occurrence critical error in firmware

- Contact Sales team and send module
for repair.

I/O LED turns off

- Failure of realization expansion Module
- None expansion Module

- Check connector status both NA
series and expansion module.

I/O LED flashes red

-Failure of configuration baud rate

- Check communication cable with
Master
- Check power for master.

-Failure of initialization I/O

- Use expansion slot up to 32.
- Compose that IO total size is not
excess.

NA series notice unidentified
expansion module ID. Check status of
expansion module.

I/O LED is red

-Failure of exchanging I/O data

Check status of expansion IO
connection.

RUN LED flashed red

-Failure of Module Configuration

Check the module hardware and
software configurations are the same.