A.3.10. 23 (0x17) read/write multiple registers, Fnio s-series – Beijer Electronics NA-9379 User Manual

Page 71

Advertising
background image

71

MODBUS Programmable I/O NA-9379

FnIO S-Series



Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr

A.3.10. 23 (0x17) Read/Write Multiple Registers

This function code performs a combination of one read operation and one write operation in a single MODBUS
transaction. The write operation is performed before the read. The request specifies the starting address and
number of holding registers to be read as well as the starting address, number of holding registers, and the data to
be written. The byte count specifies the number of bytes to follow in the write data field.
The normal response contains the data from the group of registers that were read. The byte count field specifies the
quantity of bytes to follow in the read data field.

Request

Field name

Example

RTU

ASCII

ASCII (bus line)

Start of Frame

-

t1-t2-t3

“,”

0x3A

Slave Address

0x07

0x07

“07”

0x30, 0x37

Function Code

0x17

0x17

“17”

0x31, 0x37

Read Starting Address Hi

0x08

0x08

“08”

0x30, 0x38

Read Starting Address Lo

0x00

0x00

“00”

0x30, 0x30

Quantity of Read Hi

0x00

0x00

“00”

0x30, 0x30

Quantity of Read Lo

0x02

0x02

“02”

0x30, 0x32

Write Starting Address Hi

0x08

0x08

“08”

0x30, 0x38

Write Starting Address Lo

0x00

0x00

“00”

0x30, 0x30

Quantity of Write Hi

0x00

0x00

“00”

0x30, 0x30

Quantity of Write Lo

0x02

0x02

“02”

0x30, 0x32

Byte Count

0x04

0x04

“04”

0x30, 0x34

Write Reg. Value #0 Hi

0x11

0x11

“11”

0x31, 0x31

Write Reg. Value #0 Lo

0x22

0x22

“22”

0x32, 0x32

Write Reg. Value #1 Hi

0x33

0x33

“33”

0x33, 0x33

Write Reg. Value #1 Lo

0x44

0x44

“44”

0x34, 0x34

Error Check (CRC/LRC)

-

0x88, 0x3F

“20”

0x32, 0x30

End of Frame

-

t1-t2-t3

CR, LF

0x0D, 0xA

Response

Field name

Example

RTU

ASCII

ASCII (bus line)

Start of Frame

-

t1-t2-t3

“,”

0x3A

Slave Address

0x07

0x07

“07”

0x30, 0x37

Function Code

0x17

0x17

“17”

0x31, 0x37

Byte Count

0x04

0x04

“04”

0x30, 0x34

Write Reg. Value #0 Hi

0x11

0x11

“11”

0x31, 0x31

Write Reg. Value #0 Lo

0x22

0x22

“22”

0x32, 0x32

Write Reg. Value #1 Hi

0x33

0x33

“33”

0x33, 0x33

Write Reg. Value #1 Lo

0x44

0x44

“44”

0x34, 0x34

Error Check (CRC/LRC)

-

0x2E, 0xD2

“34”

0x33, 0x34

End of Frame

-

t1-t2-t3

CR, LF

0x0D, 0xA

-

In case of address 0x0800, 0x0801 output register value: 0x0000, 0x0000 changes to 0x1122, 0x3344.