A.3.6. 6 (0x06) write single register, Fnio s-series – Beijer Electronics NA-9379 User Manual

Page 65

Advertising
background image

65

MODBUS Programmable I/O NA-9379

FnIO S-Series



Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr

A.3.6. 6 (0x06) Write Single Register
This function code is used to write a single holding register in a remote device. Therefore register numbered 1 is
addressed as 0. The normal response is an echo of the request, returned after the register contents have been
written.

Request

Field name

Example

RTU

ASCII

ASCII (bus line)

Start of Frame

-

t1-t2-t3

“,”

0x3A

Slave Address

0x07

0x07

“07”

0x30, 0x37

Function Code

0x06

0x06

“06”

0x30, 0x36

Starting Address Hi

0x08

0x08

“08”

0x30, 0x38

Starting Address Lo

0x00

0x00

“00”

0x30, 0x30

Quantity of Outputs Hi

0x11

0x11

“11”

0x31, 0x31

Quantity of Outputs Lo

0x22

0x22

“22”

0x32, 0x32

Error Check (CRC/LRC)

-

0x07, 0x85

“B8”

0x42, 0x38

End of Frame

-

t1-t2-t3

CR, LF

0x0D, 0xA

Response

Field name

Example

RTU

ASCII

ASCII (bus line)

Start of Frame

-

t1-t2-t3

“,”

0x3A

Slave Address

0x07

0x07

“07”

0x30, 0x37

Function Code

0x06

0x06

“06”

0x30, 0x36

Output Address Hi

0x08

0x08

“08”

0x31, 0x38

Output Address Lo

0x00

0x00

“00”

0x30, 0x30

Output Value Hi

0x11

0x11

“11”

0x31, 0x31

Output Value Lo

0x22

0x22

“22”

0x32, 0x32

Error Check (CRC/LRC)

-

0x07, 0x85

“B8”

0x42, 0x38

End of Frame

-

t1-t2-t3

CR, LF

0x0D, 0xA

-

In case of address 0x0800 outputs register value: 0x0000 changes to 0x1122.