Electrical - Line Voltage

WARNING!

CAUTION!

WARNING! To avoid possible injury or death due to electrical
shock, open the power supply disconnect switch and secure it
in an open position during installation.

CAUTION! Use only copper conductors for fi eld installed
electrical wiring. Unit terminals are not designed to accept other
types of conductors.

Table 4a: HT Series Electrical Data

All TT Units with Emerson ECM Fan Motor

TT Units (ECM) Standard

TT Units (ECM) with ClimaDry

Model

Compressor

HWG

Pump

FLA

Ext

Loop

Pump

FLA

Fan

Motor

FLA

Total

Unit
FLA

Min

Circuit

Amps

Max

Fuse/

HACR

(2)

ClimaDry

Pump

FLA

Total

Unit
FLA

Min

Circuit

Amps

Max/
Fuse

HACR

(2)

RLA

LRA

Qty

026

11.7

58.3

1

0.5

1.7

3.9

16.1

19.0

30

0.8

16.9

19.8

30

038

15.3

83.0

1

0.5

1.7

3.9

19.7

23.5

35

0.8

20.5

24.3

35

049

21.2

104.0

1

0.5

1.7

6.9

28.6

33.9

50

1.1

29.7

35.0

50

064

27.1

152.9

1

0.5

1.7

6.9

34.5

41.2

60

1.1

35.6

42.3

60

072

29.7

179.2

1

0.5

1.7

6.9

37.1

44.5

70

1.1

38.2

45.6

70

Rated Voltage of 208-230/60/1

Min/Max Voltage of 197/254

HACR circuit breaker in USA only

All fuses Class RK-5

HT

HT

HT

024

036

048

060

070