Cxm controls, Htv/htd/hth series, Installation, operation & maintenance – Comfort-Aire HTH Series User Manual

Page 27: Heat controller, inc

Advertising
background image

27

Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

CXM Control

For detailed control information, see CXM Application, Operation
and Maintenance (AOM) manual (part #97B0003N12).

Field Selectable Inputs

Test mode: Test mode allows the service technician to check
the operation of the control in a timely manner. By momentarily
shorting the test terminals, the CXM control enters a 20 minute
test mode period in which all time delays are sped up 15 times.
Upon entering test mode, the status LED will fl ash a code
representing the last fault. For diagnostic ease at the thermostat,
the alarm relay will also cycle during test mode. The alarm relay
will cycle on and off similar to the status LED to indicate a code
representing the last fault, at the thermostat. Test mode can be
exited by shorting the test terminals for 3 seconds.
Retry Mode: If the control is attempting a retry of a fault,
the status LED will slow fl ash (slow fl ash = one fl ash every 2
seconds) to indicate the control is in the process of retrying.

Field Confi guration Options

Note: In the following fi eld confi guration options, jumper wires
should be clipped ONLY when power is removed from the CXM
control.

Water coil low temperature limit setting: Jumper 3 (JW3-FP1 Low
Temp) provides fi eld selection of temperature
limit setting for FP1 of 30°F or 10°F [-1°F or -12°C] (refrigerant
temperature).

Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Air coil low temperature limit setting: Jumper 2 (JW2-FP2 Low
Temp) provides fi eld selection of temperature limit setting for
FP2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature).
Note: This jumper should only be clipped under extenuating
circumstances, as recommended by
the factory.

Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides fi eld
selection of the alarm relay terminal AL2 to be jumpered to 24VAC
or to be a dry contact (no connection).

Not Clipped = AL2 connected to R. Clipped = AL2 dry contact

(no connection).

DIP Switches

Note: In the following fi eld confi guration options, DIP switches
should only be changed when power is removed from the CXM
control.
DIP switch 1: Unit Performance Sentinel Disable - provides fi eld
selection to disable the UPS feature.

On = Enabled. Off = Disabled.
DIP switch 2: Stage 2 Selection - provides selection of whether
compressor has an “on” delay. If set to stage 2, the compressor
will have a 3 second delay before energizing. Also, if set for stage
2, the alarm relay will NOT cycle during test mode.

On = Stage 1. Off = Stage 2
DIP switch 3: Not Used.
DIP switch 4: DDC Output at EH2 - provides selection for DDC
operation. If set to “DDC Output at EH2,” the EH2 terminal will
continuously output the last fault code of the controller. If set to
“EH2 normal,” EH2 will operate as standard electric heat output.

On = EH2 Normal. Off = DDC Output at EH2.
NOTE: Some CXM controls only have a 2 position DIP switch
package. If this is the case, this option can be selected by
clipping the jumper which is in position 4
of SW1.

Jumper not clipped = EH2 Normal. Jumper clipped = DDC

Output at EH2.
DIP switch 5: Factory Setting - Normal position is “On.” Do not
change selection unless instructed to do so by the factory.

CXM Controls

Short test pins
together to enter Test
Mode and speed-up
timing and delays for
20 minutes.

Figure 27: Test Mode Pins

Table 6a: CXM LED And Alarm Relay Operations

Description of Operation

LED

Alarm Relay

Normal Mode

On

Open

Normal Mode with UPS Warning

On

Cycle (closed 5 sec., Open 25 sec.)

CXM is non-functional

Off

Open

Fault Retry

Slow Flash

Open

Lockout

Fast Flash

Closed

Over/Under Voltage Shutdown

Slow Flash

Open (Closed after 15 minutes)

Test Mode - No fault in memory

Flashing Code 1

Cycling Code 1

Test Mode - HP Fault in memory Flashing Code 2

Cycling Code 2

Test Mode - LP Fault in memory

Flashing Code 3

Cycling Code 3

Test Mode - FP1 Fault in memory Flashing Code 4

Cycling Code 4

Test Mode - FP2 Fault in memory Flashing Code 5

Cycling Code 5

Test Mode - CO Fault in memory Flashing Code 6

Cycling Code 6

Test Mode - Over/Under
shutdown in memory

Flashing Code 7

Cycling Code 7

Test Mode - UPS in memory

Flashing Code 8

Cycling Code 8

Test Mode - Swapped Thermistor Flashing Code 9

Cycling Code 9

-Flash code 2 = 2 quick fl ashes, 10 second pause, 2 quick

fl ashes, 10 second pause, etc.

-On pulse 1/3 second; off pulse 1/3 second

Advertising
This manual is related to the following products: