Unit Commissioning And Operating Conditions

Table 8a: Building Operating Limits

Operating Limits
Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where humidity levels could
cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).
Power Supply – A voltage variation of +/– 10% of nameplate utilization voltage is acceptable.

Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water temperature, and 3)
ambient temperature. When any one of these factors is at minimum or maximum levels, the other two factors should be at normal levels
to insure proper unit operation. Extreme variations in temperature and humidity and/or corrosive water or air will adversely affect unit
performance, reliability, and service life. Consult Table 8a for operating limits.

Commissioning Conditions
Consult Table 8b for the particular model. Starting conditions vary depending upon model and are based upon the following notes:

Notes:
1. Conditions in Table 8b are not normal or continuous operating conditions. Minimum/maximum limits are start-up conditions to bring

the building space up to occupancy temperatures. Units are not designed to operate under these conditions on a regular basis.

2. Voltage utilization range complies with AHRI Standard 110.

Table 8b: Building Commissioning Limits

Cooling

Heating

mits

mbient air, DB

45ºF [7ºC]

39ºF [4ºC]

ambient air, DB

80.6ºF [27ºC]

68ºF [20ºC]

mbient air, DB

130ºF [54ºC]

85ºF [29ºC]

tering air, DB/WB

60/45ºF [16/7ºC]

40ºF [4.4ºC]

entering air, DB/WB

80.6/66.2ºF [27/19ºC]

68ºF [20ºC]

ntering air, DB/WB

100/75ºF [38/24ºC]

80ºF [27ºC]

Limits

tering water

30ºF [-1ºC]

20ºF [-6.7ºC]

entering water

50-110ºF [10-43ºC]

30-70ºF [-1 to 21ºC]

ntering water

120ºF [49ºC]

90ºF [32ºC]

TT

perating Limits

l Water Flow

1.5 to 3.0 gpm / ton

[1.6 to 3.2 l/m per kW]

Cooling

Heating

Air Limits
Min. ambient air, DB

45ºF [7ºC]

39ºF [4ºC]

Rated ambient air, DB

80.6ºF [27ºC]

68ºF [20ºC]

Max. ambient air, DB

130ºF [54ºC]

85ºF [29ºC]

Min. entering air, DB/WB

65/45ºF [18/7ºC]

50ºF [10ºC]

Rated entering air, DB/WB

80.6/66.2ºF [27/19ºC]

68ºF [20ºC]

Max. entering air, DB/WB

100/75ºF [38/24ºC]

80ºF [27ºC]

Water Limits
Min. entering water

20ºF [-6.7ºC]

20ºF [-6.7ºC]

Normal entering water

50-110ºF [10-43ºC]

30-70ºF [-1 to 21ºC]

Max. entering water

120ºF [49ºC]

120ºF [49ºC]

Unit

Operating Limits

Normal Water Flow

1.5 to 3.0 gpm / ton

[1.6 to 3.2 l/m per kW]

70/50ºF Reheat

HT

Cooling

Heating

Air Limits
Min. ambient air, DB

45ºF [7ºC]

39ºF [4ºC]

Rated ambient air, DB

80.6ºF [27ºC]

68ºF [20ºC]

Max. ambient air, DB

130ºF [54ºC]

85ºF [29ºC]

Min. entering air, DB/WB

60ºF [16ºC]

40ºF [4.5ºC]

Rated entering air, DB/WB

80.6/66.2ºF [27/19ºC]

68ºF [20ºC]

Max. entering air, DB/WB

110/83ºF [43/28ºC]

80ºF [27ºC]

Water Limits
Min. entering water

20ºF [-6.7ºC]

20ºF [-6.7ºC]

Normal entering water

50-110ºF [10-43ºC]

30-70ºF [-1 to 21ºC]

Max. entering water

120ºF [49ºC]

120ºF [49ºC]

Unit

Commissioning Limits

Normal Water Flow

1.5 to 3.0 gpm / ton

[1.6 to 3.2 l/m per kW]