Performance Troubleshooting

Performance Troubleshooting

Htg Clg

Possible Cause

Solution

Insuffi cient capacity/ Not

cooling or heating

X

X

Dirty fi lter

Replace or clean.

X

Reduced or no air fl ow in heating

Check for dirty air fi lter and clean or replace.

Check fan motor operation and airfl ow restrictions.

Too high of external static. Check static vs. blower table.

X

Reduced or no air fl ow in cooling

Check for dirty air fi lter and clean or replace.

Check fan motor operation and airfl ow restrictions.

Too high of external static. Check static vs. blower table.

X

X

Leaky duct work

Check supply and return air temperatures at the unit and at distant duct registers
if signifi cantly different, duct leaks are present.

X

X

Low refrigerant charge

Check superheat and subcooling per chart.

X

X

Restricted metering device

Check superheat and subcooling per chart. Replace.

X

Defective reversing valve

Perform RV touch test.

X

X

Thermostat improperly located

Check location and for air drafts behind stat.

X

X

Unit undersized

Recheck loads & sizing. Check sensible clg. load and heat pump capacity.

X

X

Scaling in water heat exchanger

Perform scaling check and clean if necessary.

X

X

Inlet water too hot or too cold

Check load, loop sizing, loop backfi ll, ground moisture.

High Head Pressure

X

Reduced or no air fl ow in heating

Check for dirty air fi lter and clean or replace.

Check fan motor operation and air fl ow restrictions.

Too high of external static. Check static vs. blower table.

X

Reduced or no water fl ow in cooling

Check pump operation or valve operation/setting.

Check water fl ow. Adjust to proper fl ow rate.

X

Inlet water too hot

Check load, loop sizing, loop backfi ll, ground moisture.

X

Air temperature out of range in heating

Bring return air temperature within design parameters.

X

Scaling in water heat exchanger

Perform scaling check and clean if necessary.

X

X

Unit overcharged

Check superheat and subcooling. Re-weigh in charge.

X

X

Non-condensables in system

Vacuum system and re-weigh in charge.

X

X

Restricted metering device.

Check superheat and subcooling per chart. Replace.

Low Suction Pressure

X

Reduced water fl ow in heating.

Check pump operation or water valve operation/setting.

Plugged strainer or fi lter. Clean or replace.

Check water fl ow. Adjust to proper fl ow rate.

X

Water temperature out of range.

Bring water temperature within design parameters.

X

Reduced air fl ow in cooling.

Check for dirty air fi lter and clean or replace.

Check fan motor operation and air fl ow restrictions.

Too high of external static. Check static vs. blower table.

X

Air temperature out of range

Too much cold vent air? Bring entering air temperature within design parameters.

X

X

Insuffi cient charge

Check for refrigerant leaks.

Low Discharge Air Temperature
in Heating

X

Too high of air fl ow

Check fan motor speed selection and air fl ow chart.

X

Poor performance

See ‘Insuffi cient Capacity’

High humidity

X

Too high of air fl ow

Check fan motor speed selection and airfl ow chart.

X

Unit oversized

Recheck loads & sizing. Check sensible clg load and heat pump capacity.