Use (2) 5/16 inch, 3-inch long lag screws to

attach the straps to the wall. Replace the Tee

Cleanout Cap and screws, once the Tee is

installed.

6. Complete Chimney: Attach the Chimney

Sections as in Step 7 of the Ceiling Supported

Installation section. Secure the chimney to

the wall with Wall Straps at 4-foot intervals

to maintain at least 2 inches of clearance to

combustible materials. Slip the Wall Straps

around the chimney, tighten the bolts, and

fasten the Wall Straps to the wall with (2)

5/16-inch, 3-inch long lag screws. Snap the

Chimney Cap into the top of the chimney,

once it is at the height specified in Figure 1. If

the chimney penetrates an overhang, frame

for at least 2 inches of clearance, and install

Figure 28

WALL STRAP

ALLOW A MINIMUM OF

2 INCHES AIR SPACE

ON ALL SIDES

2 INCHES MINIMUM

2 INCHES MINIMUM

a Flashing and Storm Collar as described

in Steps 8, 9 and 10 for Ceiling Supported

Installations. Another option is to cut away

the overhang for a 2-inch clearance. (Figure

28). If the chimney extends more than 4 feet

above the top Wall Band, or Flashing, use an

Extended Roof.

7. Install Chase Cover. If a chase enclosure

has been constructed, installing the chase

cover requires some special considerations.

The chase must be ventilated at the top

and a 1/2-inch air gap must be established

between the cover, and the framed chase

top. In addition, a 1/2-inch air gap should

exist between the hole in the cover, and the

Chimney Pipe Sections. Figure 29 displays

in some detail, how these air gaps are

established with locally fabricated spacers and

covers. These are not furnished by DuraVent,

but may be made from 28 gage or heavier

sheet metal. Should the installer elect to use

Flat Roof Flashing, (which is a stock item), the

air spaces are still required. When installing

the Storm Collar, do not push it down all the

way to the cover, but allow an air space for

flow between the Chimney Pipe and the hole

in the cover.

MASONRY FIREPLACE

INSTALLATIONS

1. Determine Chimney Size: Use Table 4

to determine the correct diameter chimney for

your fireplace.

2. Mount Anchor Plate: Chimneys for

masonry fireplaces begin with an Anchor Plate.

Center the Anchor Plate on a brick or concrete

base over the masonry flue opening. Seal the

Anchor Plate with a high-temperature sealant,

and secure with (4) 1/4-inch masonry anchors.

(Figure 30). Be sure it is level. The Anchor

Plate is available in two styles. One contains

the perforated Starter Section, which is used