American Power Conversion MX28B200 User Manual

Page 36

Advertising
background image

Page 30 MX28B200/400 –48 VDC User’s Manual (990-9133)

PARAMETER NAME/

[MENU LOCATION]

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

Circuit Breaker 1 Alias
Security Level {1}
[MODULES/CIRBKR/ALIAS]



Circuit Breaker 24 Alias
Security Level {1}
[MODULES/CIRBKR/ALIAS]

An alternate name (alias) that can be
assigned to a circuit breaker if desired.




An alternate name (alias) that can be
assigned to a circuit breaker if desired.

Cir Bkr 1 m+
-48V




Cir Bkr 24 m+
-48V

Circuit Breaker 1 Tripped
Security Level {1}
[MODULES/CIRBKR/SET-
ALM]



Circuit Breaker 24 Tripped
Security Level {1}
[MODULES/CIRBKR/SET-
ALM]

An alarm that indicates Circuit Breaker 1
is tripped.





An alarm that indicates Circuit Breaker
24 is tripped.

Cir Bkr 1 Alm m+
Major





Cir Bkr 24 Almm+

Major

Compensation High Knee
Security Level {1}
[BATT/COMP]

The temperature compensation high
knee is the point above which there is no
additional battery voltage compensation
for further increases in temperature.

Comp Hknee m+
40.0 C

Compensation Low Knee
Security Level {1}
[BATT/COMP]

The temperature compensation low knee
is the point below which there is no
additional battery voltage compensation
for further decreases in temperature.

Comp Lknee m+
0.0 C

Compensation Method
Security Level {1}
[BATT/COMP]

One of three parameters that control the
DC output voltage. Activate “ON” or de-
activate “OFF” battery temperature
compensation.

Comp Method m+
OFF

Compensation Temperature
Coefficient
Security Level {1}
[BATT/COMP]

Temperature compensation coefficient
between low knee and high knee in
mV/cell/°C. (Compensation equals zero
at 25°C.)

Comp TC m+
- 3.00mV

Control Unit Revision
{Status Only}
[SYSTEM/SETUP]

Hardware revision level of the control
unit. This parameter cannot be changed.

Cntrl Rev +
000002

Date
Security Level {1}
[SYSTEM/DATE]

Internal system calendar date. Used as
a date stamp in the event log.

Date m+
DEC 16 1999

Display Type
{Status Only}
[SYSTEM/SETUP]

Type number for the control unit display.
This parameter cannot be changed.

Display Type +
000255

Fahrenheit Scale
Security Level {1}
[SYSTEM/SETUP]

Enables selection of Fahrenheit or
Celsius temperature scale (Fahrenheit
“OFF” displays readings in °C).

Fahrenheit m+
OFF

Advertising