American Power Conversion MX28B200 User Manual

Page 38

Advertising
background image

Page 32 MX28B200/400 –48 VDC User’s Manual (990-9133)

PARAMETER NAME/

[MENU LOCATION]

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

Input Relay 1
Security Level {1}
[SYSTEM/IN-RLY/RLY-MAP]



Input Relay 4
Security Level {1}
[SYSTEM/IN-RLY/RLY-MAP]

The Output Relay that is energized when
an external contact closure or opening at
the Input Relay 1 connection changes
state.



The Output Relay that is energized when
an external contact closure or opening at
the Input Relay 4 connection changes
state.

In-Rly 1 Alm m+
Ignore




In-Rly 4 Alm m+
Ignore

Input Relay 1 Alias
Security Level {1}
[SYSTEM/IN-RLY/ALIAS]



Input Relay 4 Alias
Security Level {1}
[SYSTEM/IN-RLY/ALIAS]

An alternate name (alias) can be
assigned to Input Relay 1 if desired.




An alternate name (alias) can be
assigned to Input Relay 1 if desired

In-Rly 1 m+
Input Relay 1




In-Rly 4 m+
Input Relay 4

Lamp Test
Security Level {1}
[SYSTEM/DIAG]

Setting Lamp Test to “ON” will turn on
the “MAJOR”, “MINOR”, “NORMAL”,
“MAJ”, and “MIN” LEDs on the control
unit front panel.

Lamp Test m+
OFF

LVD 1 or 2 Option
Security Level {1}
[MODULES/LVD/SET-ALM]

Must be set to “Enable” if the unit has an
LVD. If the unit has an LVD, but it is
disabled, the controller will not
disconnect the LVD.

LVD Option m+
Enable

LVD 1 or 2 Reset
Security Level {1}
[MODULES/LVD/PARAM]

LVD Reset (reconnect) threshold voltage.

LVD Reset m+
-48.00 V

LVD 1 or 2 Trip
Security Level {1}
[MODULES/LVD/PARAM]

LVD Trip (disconnect) threshold voltage.

LVD Trip m+
-42.00 V

LVD Alarm
Security Level {1}
[MODULES/LVD/SET-ALM]

The output relay that is energized when
the controller opens the LVD. If unit has
a battery LVD, no power will be available
to turn on any Output Relays.

LVD Open Alm m+
Minor

Model Programming
Security Level {2}
[SYSTEM/SETUP]

Model type number for the MX28B DC
power plant
NOTE: Changing the model number
causes the system to reinitialize.

Model m+
MX28B-200/400

OEM R Gain
Security Level {2}
[OEM]

Voltage gain adjustment for factory
calibration of system voltage
readings/settings.

OEM R Gain m+
1.000 V

OEM R Offset
Security Level {2}
[OEM]

Voltage offset adjustment for factory
calibration of system voltage
readings/settings.

OEM R Offset m+
0.000 V

OEM S Gain
Security Level {2}
[OEM]

Current gain adjustment for factory
calibration of battery current
readings/settings.

OEM S Gain m+
1.000 A