Page 34 MX28B200/400 –48 VDC User’s Manual (990-9133)

PARAMETER NAME/

[MENU LOCATION]

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

PIN Entry
Security Level {0}
[PIN]

Screen for entry of the active password
(PIN). Before any changes can be
made, the correct pin for the desires
security level must be entered. Level 0 –
full read access. Level 1 –full read and
limited write access. Level 2 – full read
and write access.

PIN m+
0000

Rectifier Communications Fail
Timeout
Security Level {1}
[MODULES/RECT/PARAM]

The maximum rectifier communications
response time allowed before a
communications failure is declared.

RectFailComm m+
1 min

Rectifier Configuration Alarm
Security Level {1}
[SYSTEM/SET-ALM]

The output relay energized if the rectifier
configuration differs from its stored
configuration. This occurs if a rectifier is
added after configuration.

Rect Cfg Alm m+
Minor

Rectifier Current Limit Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]

The output relay that is energized or
special rectifier alarm group n of N that
occurs when a rectifier has been forced
into the current limited mode.

Rect CL Alm m+
n of N

Rectifier Current Limit Alarm
Status
{Status Only}
[MODULES/RECT/INFO]

The status will be “ON” if the rectifier has
been forced into its current limited mode.
NOTE: This information can be
viewed for each rectifier installed by
using the horizontal arrow keys.

Rect 1 CL #
OFF

Rectifier Current Output Status
{Status Only}
[MODULES/RECT/INFO]

A display of the DC output current for the
individual rectifier. NOTE: This
information can be viewed for each
rectifier installed by using the
horizontal arrow keys.

Rect 1 Curr #
24.9 A

Rectifier Description
{Status Only}
[MODULES/RECT/INFO]

Displays the model number of the
installed rectifier. NOTE: This
information can be viewed for each
rectifier installed by using the
horizontal arrow keys.

Rect 1 Desc #
MRF28H54

Rectifier Fail 1-of-N Alarm
Security Level {1}
[SYSTEM/SET-ALM]

The output relay energized if Rectifier
Fail 1-of-N alarm occurs. This is a
special rectifier alarm group that signifies
that one rectifier has at least one alarm
condition.

Rect 1ofN Almm+
Minor

Rectifier Fail 2-of-N Alarm
Security Level {1}
[SYSTEM/SET-ALM]

The output relay energized if Rectifier
Fail 2-of-N alarm occurs This is a special
rectifier alarm group that signifies that
more than one rectifier has at least one
alarm condition.

Rect 2ofN Almm+
Major

Rectifier Fail Safe Voltage
Security Level {1}
[MODULES/RECT/PARAM]

Rectifier default output voltage if
communication with the control unit fails.

Rect Fail Safem+
-54.00 V

Rectifier Fan Fail Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]

The output relay that is energized or
special rectifier alarm group n of N that
occurs when a rectifier fan has failed.

Rect FF Alm m+
n of N