MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 49

voltage (54.5 VDC).

Boost/Equalize Trim Pot

The boost/equalize pot is used to adjust the
default boost equalize voltage (57.5 VDC).


6.4. Controls and Indicators


Power Shelf Control Unit

Major (Red)

On when Major Relay is de-energized*

Minor (Yellow)

On when Minor Relay is energized

Normal (Green)

On when no alarms are active

ALM 1 (Red)

On when Output Relay 1 is energized

ALM 2 (Red)

On when Output Relay 2 is energized

ALM 3 (Red)

On when Output Relay 3 is energized

ALM 4 (Red)

On when Output Relay 4 is energized

ALM 5 (Red)

On when Output Relay 5 is energized

ALM 6 (Red)

On when Output Relay 6 is energized

MIN (Red)

On when Minor Relay is energized

MAJ (Red)

On when Major Relay is de-energized*


6.5. Mechanical

Dimensions

15.75” high x 23” wide x 17.5” deep (MX28B-200)

22.75” high x 23” wide x 17.5” deep (MX28B-400)

Housing

85 lbs. (MX28B-200)
110 lbs. (MX28B-400)

Weight

Rectifier (each)

11 lbs

Color

Dawn Gray

Advertising