MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 35

PARAMETER NAME/

[MENU LOCATION]

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

Rectifier Fan Fail Alarm Status
{Status Only}
[MODULES/RECT/INFO]

The status will be “ON” if the rectifier fan
has failed. NOTE: This information
can be viewed for each rectifier
installed by using the horizontal arrow
keys.

Rect 1 FF #
OFF

Rectifier Fault Alarm (RFA)
Status
{Status Only}
[MODULES/RECT/INFO]

The status will be on if the rectifier output
has failed. NOTE: This information
can be viewed for each rectifier
installed by using the horizontal arrow
keys.

Rect 1 RFA #
OFF

Rectifier RFA Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]

The output relay that is energized or
special rectifier alarm group n of N that
occurs when a rectifier output has failed.

Rect RFA Alm m+
n of N

Rectifier Standby Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]

The output relay that is energized or
special rectifier alarm group n of N that
occurs when the control unit is holding a
rectifier in the standby mode.

Rect Stdby Almm+
n of N

Rectifier Standby Alarm Status
{Status Only}
[MODULES/RECT/INFO]

The status will be “ON” if the control unit
is holding the rectifier in the standby
mode. NOTE: This information can be
viewed for each rectifier installed by
using the horizontal arrow keys.

Rect 1 Stdby #
OFF

Store Configuration
Security Level {1}
[SYSTEM/DIAG]

Setting this parameter to “Enable” will
cause the current rectifier configuration
to be stored (the display toggles back to
“Disable” after entry).

Store Cfg m+
Disable

System Current
{Status Only}
[STATUS]

The total system output current
(calculated as the sum of the individual
rectifier output currents).

Sys Current +
145.8 A

System High Temperature
Alarm
Security Level {1}
[SYSTEM/SET-ALM]

The output relay energized if the System
Temperature exceeds the system high
temperature threshold.

Sys HT Alm m+
Minor

System High Temperature
Threshold
Security Level {1}
[SYSTEM/SET-ALM]

System Temperature is ambient
temperature measured inside the
controller. An alarm will be reported if
temperature is higher than the
temperature entered.

Sys HT Thr m+
70.0 C

System High Voltage alarm
Security Level {1}
[SYSTEM/SET-ALM]

The output relay energized if the System
Voltage is above the System High
Voltage threshold.

Sys HV Alm m+
Minor

System High Voltage
Threshold
Security Level {1}
[SYSTEM/SET-ALM]

System Voltage is bus voltage measured
by the controller. An alarm will be
reported if voltage is higher than the
voltage entered.

Sys HV Thr m+
-58.00 V

System Low Temperature
Alarm
Security Level {1}
[SYSTEM/SET-ALM]

The output relay energized if the System
Temperature is below the System Low
Temperature threshold.

Sys LT Alm m+
Minor