American Power Conversion MX28B200 User Manual

Page 37

Advertising
background image

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 31

PARAMETER NAME/

[MENU LOCATION]

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

Firmware Version
{Status Only}
[SYSTEM/SETUP]

Version number of the control unit
firmware.
NOTE: Actual firmware version
number displayed is the current
version as of the date of manufacture.

This parameter cannot be changed.

FW Version +
000189

GMT 1 Alias
Security Level {1}
[MODULES/GMT/ALIAS]



GMT 8 Alias
Security Level {1}
[MODULES/GMT/ALIAS]

An alternate name (alias) that can be
assigned to a GMT Fuse 1 if desired.




An alternate name (alias) that can be
assigned to a GMT Fuse 8 if desired.

GMT 1 m+
-48V




GMT 8 m+
-48V

GMT 1 Blown
Security Level {1}
[MODULES/GMT/SET-ALM]



GMT 8 Blown
Security Level {1}
[MODULES/GMT/SET-ALM]

The Output Relay that is energized when
GMT Fuse 1 is blown.




The Output Relay that is energized when
GMT Fuse 8 is blown.

GMT 1 Alm m+
Major




GMT 8 Alm m+
Major

Hardware Battery Current
Alarm
Security Level {2}
[SYSTEM/SET-ALM]

The output relay energized if there is a
hardware failure in the battery current
monitoring function.

Hw Batt C Almm+
Minor

Hardware Battery Temperature
Alarm
Security Level {2}
[SYSTEM/SET-ALM]

The output relay energized if there is a
hardware failure in the battery
temperature monitoring function.

Hw Batt T Almm+
Minor

Hardware LVD Alarm
Security Level {2}
[SYSTEM/SET-ALM]

The output relay energized if there is a
conflict between the commanded and
sensed positions of the LVD contactor.
Generally the contactor is open when it
should be closed.

Hw LVD Alm m+
Minor

Hardware System Temperature
Alarm
Security Level {2}
[SYSTEM/SET-ALM]

The output relay energized if there is a
hardware failure in the system
temperature monitoring function.

Hw Sys T Alm m+
Minor

Hardware System Voltage
Alarm
Security Level {2}
[SYSTEM/SET-ALM]

The output relay energized if there is a
hardware failure in the system voltage
monitoring function.

Hw Sys V Alm m+
Minor

Advertising