Installation at different levels, Connection piping for remote condensing units – American Panel HURRICHILL AP120BCF1300-3 User Manual
Page 7
Advertising
AP120BC1000-3/ AP120BCF1300-3 Manual
6
INSTALLATION AT DIFFERENT LEVELS
If the remote condensing unit is installed at a higher level than the cabinet (FIG. 6) insert a siphon
in the return line at every 6 ft. of difference in height. If the remote condensing unit is installed at a
lower level than the cabinet (FIG. 7) it is not necessary to insert any siphons.
FIG. 6
FIG. 7
Insert a siphon at the beginning (a) and at the end (b) of each riser
CONNECTION PIPING FOR REMOTE CONDENSING UNITS
MODEL
SUPPLY LINE DIA.
INTAKE LINE DIA.
AP120BC1000-3 7/8”
2 1/8”
AP120BCF1300-3
1 1/8”
2 1/8”
Advertising