INSTALLATION AT DIFFERENT LEVELS

If the remote condensing unit is installed at a higher level than the cabinet (FIG. 6) insert a siphon
in the return line at every 6 ft. of difference in height. If the remote condensing unit is installed at a
lower level than the cabinet (FIG. 7) it is not necessary to insert any siphons.

FIG. 6

FIG. 7

Insert a siphon at the beginning (a) and at the end (b) of each riser

CONNECTION PIPING FOR REMOTE CONDENSING UNITS

MODEL

SUPPLY LINE DIA.

INTAKE LINE DIA.

AP120BC1000-3 7/8”

2 1/8”

AP120BCF1300-3

1 1/8”

2 1/8”