Table 2 – Maximum Gas Flow Capacity*

NOMINAL

IRON PIPE

SIZE (IN.)

INTERNAL

DIAMETER

(IN.)

LENGTH OF PIPE ft (m)†

10

(3.0)

20

(6.1)

30

(9.1)

40

(12.1)

50

(15.2)

60

(18.3)

70

(21.3)

80

(24.4)

90

(27.4)

100

(30.5)

125

(38.1)

150

(45.7)

175

(53.3)

200

(61.0)

1/2

.622

175

120

97

82

73

66

61

57

53

50

44

40

3/4

.824

360

250

200

170

151

138

125

118

110

103

93

84

77

72

1

1.049

680

465

375

320

285

260

240

220

205

195

175

160

145

135

1---1/4

1.380

1400

950

770

600

580

530

490

460

430

400

360

325

300

280

1---1/2

1.610

2100

1460

1180

990

900

810

750

690

650

620

550

500

460

430

*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5---IN. W.C. (based on a 0.60 specific gravity gas). Refer to Table 2

and NFPA 54/ANSI Z223.1.
{

This length includes an ordinary number of fittings.

ROUTING CONTROL POWER WIRES
For detailed instruction on the low voltage connections to the User

Interface (UI), refer to the UI installation guide.
Form a drip--loop with the control leads before routing them into

the unit. Route the low voltage control leads through grommeted,

low--voltage hole provided into unit (See Fig. 5 and 6). Connect
user interface leads to unit control power leads as shown in Fig. 14.
The unit transformer supplies 24--v power for complete system
including accessory electrical heater. Transformer is factory wired

for 230--v operation. If supply voltage is 208--v, rewire transformer

primary as described in Special Procedures for 208--v Operation
section.
The furnace board is fused by a board--mounted automotive fuse
placed in series with transformer SEC1 and R circuit. The C circuit

of transformer circuit is referenced to chassis ground through a

printed circuit run at SEC2 and gas valve grounding wire. Check to
be sure control board is mounted securely using both

factory--installed screws.
ACCESSORY INSTALLATION

A. Outdoor Air Temperature Sensor (OAT)

EQUIPMENT OPERATION HAZARD
The installation of an outdoor air temperature sensor (OAT)

using the Evolution control board OAT terminals is

required. Many Evolution features (auto humidity control,

comfort rollback, etc.) will be lost if the OAT is not

connected.
For detailed mounting instructions for the OAT sensor,

please refer installation instructions shipped with the OAT.

!

CAUTION

The OAT input is used to supply outdoor temperature data for
system level functions and for temperature display on User

Interface (UI). Using two wires of the field--supplied thermostat
wire cable, wire the ends of the two black OAT pigtails. Wire the

opposite ends of these two wires to the OAT provided with the UI.

There is no polarity to be observed.
NOTE: Mis--wiring OAT inputs will not cause damage to either
Evolution control or thermistor. If the thermistor is wired
incorrectly, no reading will appear at UI. Re--wire thermistor
correctly for normal operation.

B. Humidifier Connections

The furnace control board terminal marked HUM is provided for

low voltage (24--vac) control of a humidifier. No humidistat is
required as UI monitors indoor humidity.
When commanded to operate humidifier, the unit control will
energize the HUM output to turn humidifier on and de--energize

HUM output to turn humidifier off. Wire HUM and COM

terminals directly to humidifier as shown in Fig. 14.

C. Electronic Air Cleaner

Electronic Air Cleaner terminals are provided on the Evolution
Control Board (EAC--1 and EAC--2). While these terminals can be

used to power a 230V EAC, it is recommended that any EAC be
installed per the EAC installation instructions and connected

separately to a standard 115V or 230V outlet with an airflow
sensor to control operation of the EAC.
SPECIAL PROCEDURES FOR 208--V OPERATION
Be sure unit disconnect switch is open.
Disconnect the black primary lead from the transformer. See unit

wiring label (See Fig. 16 and 17).
Connect the black primary lead to the transformer terminal labeled

208--v.