STATUS CODE 21 -- GAS HEATING LOCKOUT
Control will NOT auto reset. Check for mis--wired gas valve or

defective control (valve relay).
STATUS CODE 22 -- ABNORMAL FLAME--PROVING

SIGNAL

Flame is proved while gas valve is de--energized. Inducer will run
until fault is cleared. Check for leaky gas valve or stuck--open gas

valve.
STATUS CODE 23 -- PRESSURE SWITCH DID NOT OPEN

Check for obstructed pressure tubing or pressure switch stuck

closed.
STATUS CODE 24 -- SECONDARY VOLTAGE FUSE IS OPEN

Check for short circuit in secondary voltage (24VAC) wiring.
STATUS CODE 25 -- INVALID MODEL SELECTION OR

SETUP ERROR

Indicates either the model plug is missing or incorrect. If code
flashes 4 times on power--up, control is defaulting to model

selection stored in memory. Check for proper model plug number
and resistance values per wiring diagram.
STATUS CODE 31, 32 -- PRESSURE SWITCH OR RELAY DID
NOT CLOSE OR REOPENED

Control relay may be defective. If open longer than five minutes,

inducer shuts off for 15 minutes before retry. If open during blower
on--delay period, blower will come on for the selected blower

off--delay. Check for excessive wind, restricted vent, defective
inducer motor, defective pressure switch, lower inducer voltage

(230VAC), inadequate combustion air supply, disconnected or

obstructed pressure tubing, or low inlet gas pressure (if LGPS
used).
STATUS CODE 33 -- LIMIT CIRCUIT FAULT
Indicates a limit or flame rollout switch is open. Blower will run

for 4 minutes or until open switch remakes, whichever is longer. If

open longer than 3 minutes, code changes to lockout 13. If open
less than 3 minutes status code 33 continues to flash until blower

shuts off. Check for loose blower wheel, restricted vent, excessive
wind, dirty filter or restricted duct system, defective switch or

connections, or inadequate combustion air supply (flame roll--out
switch open).
STATUS CODE 34 -- IGNITION PROVING FAILURE

Control will try three more times before lockout 14 occurs. If flame
signal lost during blower on--delay period, blower will come on for

the selected blower off--delay. Check for oxide buildup on flame
sensor (clean with fine steel wool), proper flame sense microamps

(.5 microamps D.C. min., 4.0--6.0 nominal), manual valve shutoff,

low inlet gas pressure, control ground continuity, gas valve
defective or turned off, flame sensor must not be grounded,

inadequate flame carryover or rough ignition, or green/yellow wire
must be connected to unit sheet metal.
STATUS CODE 41 -- BLOWER MOTOR FAULT

Indicates the blower failed to reach 250 RPM or the blower failed
to communicate within the prescribed time limits. Thirty seconds

after being turned ON or ten seconds during steady--state
operation.
STATUS CODE 42 -- INDUCER MOTOR FAULT
Indicates inducer motor hasn’t started within a prescribed time

limit. Check inducer motor and wiring.
STATUS CODE 45 -- CONTROL CIRCUITRY LOCKOUT
Auto reset after one hour lockout due to gas valve relay stuck open,

flame sense circuit failure, or software check error. Reset power to
clear lockout. Replace control if status code repeats.

E. HP/AC Control Troubleshooting

See Table 4 for HP/AC control board status codes and

troubleshooting information.
STATUS CODE 53, OUTDOOR AIR TEMPERATURE
SENSOR FAULT -- DETAILED DESCRIPTION