577d -- -- a – Bryant EVOLUTION 577D----A User Manual

Page 24

Advertising
background image

24

Table 3 – Air Delivery and Temperature Rise at Rated Heating Input

Unit

Rated Heating Input (Btu/hr)

Heating Rise Range

o

F (

o

C)

Heating Rise Either Stage, °F (

o

C)

High Stage

Low Stage

High Stage

Low Stage

“Efficiency”

“Comfort”

High Stage

Low Stage

High Stage

Low Stage

577DNWA24040

577DNWA30040

40,000

26,000

20 --- 50

(11---28)

15---45

(8---25)

35

(19)

30

(17)

40

(22)

35

(19)

577DNWA30060

577DNWA36060

577DNWA42060

60,000

39,000

25 --- 55

(14---31)

25 --- 55

(14---31)

40

(22)

50

(28)

577DNWA36090

577DNWA42090

577DNWA48090

577DNWA60090

90,000

58,500

35 --- 65

(19---36)

35 --- 65

(19---36)

50

(28)

55

(31)

577DNWA48115

577DNWA60115

115,000

75,000

30 --- 60

(17---33)

30 --- 60

(17---33)

45

(25)

50

(28)

577DNWA48130

577DNWA60130

130,000

84,500

35 --- 65

(19---36)

35 --- 65

(19---36)

50

(28)

55

(31)

Airflow delivery values for external static pressure values of up to 1 IN. W.C.

Table 4 – Heat Pump/Air Conditioner Board Status Codes

OPERATION

FAULT

AMBER LED

FLASH

CODE

POSSIBLE CAUSE AND ACTION

Standby – no call for unit operation

None

On solid, no

flash

Normal operation.

Emergency Mode

Standard Thermo-

stat Control

Rapid, con-

tinuous

flashing

Unit being controlled by standard thermostat inputs instead of Evolution

Control. Only high stage operation is available. This operating mode

should be used in emergency situations only.

Low Stage Cool/Heat Operation

None

1, pause

Normal operation.

High Stage Cool/Heat Operation

None

2, pause

Normal operation.

System Communica-

tions Failure

16

Communication with UI lost. Check wiring to UI, indoor and outdoor units.

Invalid Model Plug

25

Control does not detect a model plug or detects an invalid model plug. Unit

will not operate without correct model plug.

High---Pressure

Switch Open

31

High---pressure switch trip. Check refrigerant charge, outdoor fan operation

and coils for airflow restrictions.

Low---Pressure

Switch Open

32

Low---pressure switch trip. Check refrigerant charge and indoor air flow.

Control Fault

45

Outdoor unit control board has failed. Control board needs to be replaced.

Brown Out

(230 v)

46

Line voltage < 187v for at least 4 seconds. Compressor and fan operation

not allowed until voltage>190v. Verify line voltage.

No 230v at Unit

47

There is no 230v at the contactor when indoor unit is powered and cooling/

heating demand exists. Verify the disconnect is closed and 230v wiring is

connected to the unit.

Outdoor Air Temp

Sensor Fault

53

Outdoor air sensor not reading or out of range. Ohm out sensor and check

wiring.

Outdoor Coil Sensor

Fault

55

Coil sensor not reading or out of range. Ohm out sensor and check wiring.

Thermistors Out of

Range

56

Improper relationship between coil sensor and outdoor air sensor. Ohm out

sensors and check wiring.

Low Stage Thermal

Cutout

71

Compressor voltage sensed, then disappears while cooling or heating de-

mand exists. Possible causes are internal compressor overload trip or start

relay not releasing (if installed).

High Stage Thermal

Cutout

72

Compressor voltage sensed, then disappears while cooling or heating de-

mand exists. Possible causes are internal compressor overload trip or start

relay not releasing (if installed).

Contactor Shorted

73

Compressor voltage sensed when no demand for compressor operation

exists. Contactor may be stuck closed or there is a wiring error.

No 230V at Com-

pressor

74

Compressor voltage not sensed when compressor should be starting. Con-

tactor may be stuck open or there is a wiring error.

Low Stage Thermal

Lockout

81

Thermal cutout occurs in three consecutive low/ high stage cycles. Low

stage locked out for 4 hours or until 24v power recycled.

High Stage Thermal

Lockout

82

Thermal cutout occurs in three consecutive high/low stage cycles. High

stage locked out for 4 hours or until 24v power recycled.

Low---Pressure Lock-

out

83

Low---pressure switch trip has occurred during 3 consecutive cycles. Unit

operation locked out for 4 hours or until 24v power recycled.

High---Pressure

Lockout

84

High---pressure switch trip has occurred during 3 consecutive cycles. Unit

operation locked out for 4 hours or until 24v power recycled.

577D

--

--

A