Table 10 – Troubleshooting Chart -- Gas Furnace Operation

SYMPTOM

CAUSE

REMEDY

Burners will not ignite

Water in gas line

Drain. Install drip leg.

No power to unit

Check power supply fuses, wiring or circuit

breaker.

No 24--v power supply to control circuit

Check transformer.

NOTE: Some transformers have internal over--

current protection that requires a cool--down peri-

od to reset.

Mis--wired or loose connections

Check all wiring and wire nut connections

Misaligned spark electrodes

Check flame ignition and sense electrode posi-

tioning.

Adjust as necessary.

No gas at main burners

1. Check gas line for air. Purge as necessary.

NOTE: After purging gas line of air, wait at least 5

minutes for any gas to dissipate before attempt-

ing to light unit.

2. Check gas valve.

Inducer pressure switch not closing

1. Check pressure switch wires, connections,

and tubing. Repair or replace if necessary.

Inadequate heating

Dirty air filter

Clean or replace filter as necessary

Gas input to unit too low

Check gas pressure at manifold match with that

on unit nameplate

Unit undersized for application

Replace with proper unit or add additional unit

Restricted airflow

Clean or replace filter. Remove any restriction.

Limit switch cycles main burners

Check rotation of blower, temperature rise of unit.

Adjust as necessary.

Poor flame characteristics

Incomplete combustion results in: Aldehyde odors,

carbon monoxide, sooting flame, floating flame

1. Tighten all screws around burner compartment

2. Cracked heat exchanger. Replace.

3. Unit over--fired. Reduce input (change orifices

or adjust gas line or manifold pressure).

4. Check burner alignment.

5. Inspect heat exchanger for blockage. Clean

as necessary.