3 input port connections – Barnett Engineering Pro Talk ARU CV2 User Manual

Page 11

Advertising
background image

Installation

2-2

B1272M001

BARNETT ENGINEERING LTD.

ProTalk Cv2

Figure 3 Stand-alone Cv2

Figure 4 Ground Closure Input Wiring

2.2.2 Stand-alone model

The stand-alone Cv2 can be mounted on a flat surface. Make sure that there is enough room
around the unit to make connections. The environment should be clean and dry, with an

ambient temperature that
does not go below -20

o

C

or above +50

o

C.

Connect a DC power
source to the terminals on
TB2. The Cv2 requires up
to 1.5 Amps to operate;
the supply should be sized
accordingly. Input power
to the unit is protected by
a Polyswitch current
limiter. If a fault develops
in the CV2, this switch
will become a high

resistance to prevent damage to the equipment or the power supply. Once this switch has
been activated, the fault must be removed before it will reset and allow current to pass through
to the equipment.

Connect the antenna or coaxial feed line to the remote antenna onto the TNC coaxial jack on
the Cv2.

Connect the input and output signal lines between the Cv2 and the equipment that you want to
monitor and control. Details of the input and output ports are discussed in the next section.

2.3 Input port connections

The input ports can be connected to a variety of contact or voltage sources for monitoring
purposes. Select a wiring configuration that matches your alarm source from one of the
following arrangements:

2.3.1 Ground closure alarm signal

For alarm sources that appear as a ground
closure, either through a mechanical contact
or an open collector driver, the input should
be wired according to Figure 4. If the input
is normally open and goes to ground during
an alarm condition, program the Hardware
section for this input as “Normally High”. If
the reverse is true, set the input to “Normally
Low”.