Configuration using the PC

3-16

B1272M001

BARNETT ENGINEERING LTD.

ProTalk Cv2

Auto Ack

If enabled for the group using this directory, the Auto Ack command causes the Cv2 to
automatically acknowledge its alarms without receipt of any other code or signal. This
command is used when it is anticipated that the called party will have no means of
acknowledging the call. Unless absolutely necessary, this command should not be used
since there is no assurance that the alarm message was properly received.

The Auto Ack command should be the last entry in the directory and must appear on a line
by itself.

DTMF

The DTMF command will result in the string of DTMF digits in the associated Value field
being transmitted. The maximum length of the DTMF string is 39 characters and the
characters can be any of the 16 digits including A, B, C, and D. The special character ‘!’
can be inserted anywhere in the DTMF string to create a two second delay.

DTMF must be preceded by a Dial command; it cannot be the first entry in the list. It can
be used more than once in a list.

Default DTMF value: 0000

Alert

The Alert command generates a tone sequence that is used to alert the called party that a
message will follow. The tone sequence consists of eight 100 msec bursts of 1 kHz tone
separated by 100 msec of quiet.

Alert must be preceded by a Dial command; it cannot be the first entry in the list. It can be
used more than once in a list.

Voice

The Voice command causes stored voice messages for the Site ID, Group IDs and any
points in the alarm state to be spoken. If Voice is the only command after Dial, the Cv2
will speak the alarm message three times or for one minute, whichever comes first. If other
commands are used, either before or after Voice, the messages will be spoken once.

Voice must be preceded by a Dial command; it cannot be the first entry in the list. It can be
used only once in a list.

Answer

The Answer command causes the Cv2 to monitor the called line for activity before it begins
to speak the alarm message. If the Cv2 is calling a voice or numeric paging terminal with
an automated attendant, the Answer command will cause it to wait for the voice prompt
before transmitting the pager number. Do not place the Answer command immediately
after a Dial command if Call Progress is selected in the General section. This will cause
the Cv2 to look for a voice response twice in a row and may prevent alarm announcements.