Bryant DuraPac Series 580f User Manual

Page 12

Advertising
background image

12

Table 2A — Electrical Data (Without Convenience Outlet)

LEGEND

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer

to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

3. For units with power exhaust: If a single power source is to be used, size wire to include

power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered
through the unit (must be in accordance with NEC and/or local codes). Determine the new
MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A00 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is
acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next
larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

UNIT
580F

NOMINAL
VOLTAGE

IFM

TYPE

VOLTAGE

RANGE

COMPR

(ea)

OFM

(ea)

IFM

COMBUSTION

FAN MOTOR

FLA

POWER SUPPLY

DISCONNECT

SIZE*

Min

Max

RLA

LRA

Hp

FLA

FLA

MCA

MOCP†

FLA

LRA

036

(3 Tons)

208/230-1-60

Std

187

254

16.2

96.0

1

/

4

1.4

3.5

.6

25.2/25.2

30/30

24/24

106/106

Alt

4.9

26.6/26.6

35/35

26/26

111/111

208/230-3-60

Std

187

254

10.2

75.0

1

/

4

1.4

3.5

.6

17.7/17.7

25/25

17/17

85/ 85

Alt

4.9

19.1/19.1

25/25

19/19

90/ 90

High

5.2

19.4/19.4

25/25

19/19

109/109

460-3-60

Std

414

508

4.4

40.0

1

/

4

0.8

1.3

.3

7.6

15

7

44

Alt

2.1

8.4

15

8

48

High

2.6

8.9

15

9

57

575-3-60

Std

518

632

3.7

31.0

1

/

4

0.8

1.3

.3

5.5

15

6

35

Alt

2.1

6.0

15

7

37

High

2.6

6.3

15

7

56

048

(4 Tons)

208/230-1-60

Std

187

254

23.3

118.0

1

/

4

1.4

3.5

.6

34.0/34.0

40/40

32/32

129/129

Alt

4.9

35.4/35.4

45/45

34/34

133/133

208/230-3-60

Std

187

254

15.4

90.0

1

/

4

1.4

3.5

.6

24.2/24.2

30/30

23/23

101/101

Alt

4.9

25.6/25.6

30/30

25/25

105/105

High

5.2

25.9/25.9

30/30

25/25

124/124

460-3-60

Std

414

508

8.3

45.0

1

/

4

0.8

1.8

.3

13.0

20

13

51

Alt

2.1

13.3

20

13

53

High

2.6

13.8

20

13

62

575-3-60

Std

518

632

6.4

36.0

1

/

4

0.8

1.8

.3

9.2

15

10

41

Alt

2.1

9.3

15

10

42

High

2.6

9.7

15

10

49

060

(5 Tons)

208/230-1-60

Std

187

254

28.8

147.0

1

/

4

1.4

5.9

.6

43.3/43.3

60/60

42/42

161/161

Alt

6.6

44.0/44.0

60/60

42/42

184/184

208/230-3-60

Std

187

254

16.0

114.0

1

/

4

1.4

5.9

.6

27.3/27.3

35/35

27/27

128/128

Alt

5.2

26.6/26.6

35/35

26/26

148/148

High

7.5

28.9/28.9

35/35

29/29

174/174

460-3-60

Std

414

508

7.4

64.0

1

/

4

0.8

3.1

.3

13.2

20

13

71

Alt

2.6

13.5

20

13

81

High

3.4

13.5

20

13

93

575-3-60

Std

518

632

6.2

52.0

1

/

4

0.8

3.1

.3

9.7

15

11

58

Alt

2.6

9.9

15

11

65

High

3.4

9.9

15

11

76

072

(6 Tons)

208/230-3-60

Std

187

254

20.6

146.0

1

/

4

1.4

5.2

.6

32.4/32.4

40/40

31/31

180/180

High

7.5

34.7/34.7

40/40

34/34

205/205

460-3-60

Std

414

508

9.5

73.0

1

/

4

0.9

2.6

.3

15.4

20

15

90

High

3.4

16.2

20

16

103

575-3-60

Std

518

632

7.6

58.4

1

/

4

0.6

2.6

.3

11.4

15

12

75

High

3.4

11.9

15

13

86

073

(6 Tons)

208/230-3-60

Std

187

254

20.6

146.0

1

/

4

1.4

5.2

.6

32.4/32.4

40/40

31/31

180/180

High

7.5

34.7/34.7

40/40

34/34

205/205

460-3-60

Std

414

508

9.5

73.0

1

/

4

0.9

2.6

.3

15.4

20

15

90

High

3.4

16.2

20

16

103

575-3-60

Std

518

632

7.6

58.4

1

/

4

0.6

2.6

.3

11.4

15

12

79

High

3.4

11.9

15

13

86

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

% Voltage Imbalance = 100 x

7

457

POWER EXHAUST

PART NO.

MCA

(230 v)

MCA

(460 v)

MCA

(575 v)

MOCP

(for separate

power source)

CRPWREXH030A00

1.6

N/A

0.64

15

CRPWREXH021A00

N/A

0.9

N/A

15

CRPWREXH022A00

3.3

N/A

1.32

15

CRPWREXH023A00

N/A

1.8

N/A

15

CRPWREXH028A00

1.7

N/A

0.68

15

CRPWREXH029A00

N/A

1.0

N/A

15

Advertising