Bryant DuraPac Series 580f User Manual

Page 55

Advertising
background image

55

Table 41 — LED Error Code Service Analysis

IMPORTANT:

Refer to Table 42 — Heating Service Analysis for additional

troubleshooting analysis.

LEGEND

Table 42 — Heating Service Analysis

SYMPTOM

CAUSE

REMEDY

Hardware Failure.
(LED OFF)

Loss of power to control module (IGC).

Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
transformer. Units without a 24-v circuit breaker have an internal overload
in the 24-v transformer. If the overload trips, allow 10 minutes for automatic
reset.

Fan ON/OFF Delay Modified
(LED/FLASH)

High limit switch opens during heat exchanger
warm-up period before fan-on delay expires.
Limit switch opens within three minutes after
blower-off delay timing in Heating mode.

Ensure unit is fired on rate and temperature rise is correct.

Ensure unit’s external static pressure is within application guidelines.

Limit Switch Fault.
(LED 2 flashes)

High temperature limit switch is open.

Check the operation of the indoor (evaporator) fan motor.
Ensure that the supply-air temperature rise is in accordance with the range
on the unit nameplate.

Flame Sense Fault.
(LED 3 flashes)

The IGC sensed flame that should not be
present.

Reset unit. If problem persists, replace control board.

4 Consecutive Limit
Switch Faults.
(LED 4 flashes)

Inadequate airflow to unit.

Check operation of indoor (evaporator) fan motor and that supply-air
temperature rise agrees with range on unit nameplate information.

Ignition Lockout.
(LED 5 flashes)

Unit unsuccessfully attempted ignition for
15 minutes.

Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that flame sense and ignition wires are properly terminated. Verify
that unit is obtaining proper amount of gas.

Induced-Draft Motor Fault.
(LED 6 flashes)

IGC does not sense that induced-draft
motor is operating.

Check for proper voltage. If motor is operating, check the speed sensor
plug/IGC Terminal J2 connection. Proper connection: PIN 1 — White, PIN
2 — Red, PIN 3 — Black.

Rollout Switch Fault.
(LED 7 flashes)

Rollout switch has opened.

Rollout switch will automatically reset, but IGC will continue to lockout unit.
Check gas valve operation. Ensure that induced-draft blower wheel is prop-
erly secured to motor shaft.
Reset unit at unit disconnect.

Internal Control Fault.
(LED 8 flashes)

Microprocessor has sensed an error in the
software or hardware.

If error code is not cleared by resetting unit power, replace the IGC.

Internal Software Fault.
(LED 9 flashes)

Internal Software Processor fault.

Fault code will automatically reset after one hour. Can be immediately
reset by resetting unit power supply.

CAUTION:

If the IGC must be replaced, be sure to ground

yourself to dissipate any electrical charge that may be present before
handling new control board. The IGC is sensitive to static electricity
and may be damaged if the necessary precautions are not taken.

IGC

Integrated Gas Unit Controller

LED

Light-Emitting Diode

PROBLEM

CAUSE

REMEDY

Burners Will Not Ignite.

Misaligned spark electrodes.

Check flame ignition and sensor electrode positioning. Adjust as needed.

No gas at main burners.

Check gas line for air, purge as necessary. After purging gas line of air, allow
gas to dissipate for at least 5 minutes before attempting to relight unit.

Check gas valve.

Water in gas line.

Drain water and install drip leg to trap water.

No power to furnace.

Check power supply, fuses, wiring, and circuit breaker.

No 24 v power supply to control circuit.

Check transformer. Transformers with internal overcurrent protection require a
cool down period before resetting.

Miswired or loose connections.

Check all wiring and wire nut connections.

Burned-out heat anticipator in thermostat.

Replace thermostat.

Broken thermostat wires.

Run continuity check. Replace wires, if necessary.

Inadequate Heating.

Dirty air filter.

Clean or replace filter as necessary.

Gas input to unit too low.

Check gas pressure at manifold. Clock gas meter for input. If too low, increase
manifold pressure, or replace with correct orifices.

Unit undersized for application.

Replace with proper unit or add additional unit.

Restricted airflow.

Clean filter, replace filter, or remove any restrictions.

Blower speed too low.

Use high speed tap, increase fan speed, or install optional blower, as suitable
for individual units.

Limit switch cycles main burners.

Check rotation of blower, thermostat heat anticipator settings, and temperature
rise of unit. Adjust as needed.

Too much outdoor air.

Adjust minimum position.

Check economizer operation.

Poor Flame Characteristics.

Incomplete combustion (lack of combustion
air) results in:
Aldehyde odors, CO, sooting flame, or floating
flame.

Check all screws around flue outlets and burner compartment. Tighten as nec-
essary.

Cracked heat exchanger.

Overfired unit — reduce input, change orifices, or adjust gas line or manifold
pressure.

Check vent for restriction. Clean as necessary.

Check orifice to burner alignment.

Burners Will Not Turn Off.

Unit is locked into Heating mode for a one
minute minimum.

Wait until mandatory one minute time period has elapsed or re-
set power to unit.

Advertising