Table 35 — economi$er+ inputs and outputs, Fig. 36 — economi$er+ controller board – Bryant DuraPac Series 580f User Manual

Page 40

Advertising
background image

40

Table 35 — EconoMi$er+ Inputs and Outputs

*If there are 3 stages then there can only be 1 stage of power exhaust.
†If there are 4 stages then no power exhaust stages are directly controlled.

INPUT

NAME

TYPE

USE

INPUT/OUTPUT

RANGE

CONVERSION

RANGE

CONVERSION

RESOLUTION

CONNECTION

PIN
NO.

THERMOSTAT INPUTS
Y1 (Cool/Low Cool)

Y1

Switch

Standard

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

1

Y2 (Cool 2/High Cool)

Y2

Switch

Option

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

2

G (fan)

G

Switch

Standard

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

3

Occupied/Unoccupied

OCC

Switch

Option

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

4,5

POWER
Power

24V

Input

Standard

18-30 VAC 50/60 Hz

NA

NA

J2

1,2

ECONOMIZER MOTOR
Control

CNT

2-10 vdc

Standard

2-10 vdc

0-100%

1%

J2

3,4,5

ANALOG INPUTS
Supply Air Temperature

SAT

10 K Thermistor

Standard

1816 to 86407 Ohms

30 to 125 F

0.8 F

J3

1,2

Outside Air
Temperature

OAT

10 K Thermistor

Standard

1816 to 86407 Ohms

30 to 125 F

0.8 F

J3

3,4

Return Air Temperature

RAT

10 K Thermistor

Option

1816 to 86407 Ohms

30 to 125 F

0.8 F

J3

5,6

Indoor Humidity

IRH

4-20 mA,

Loop Powered

Option

4-20 mA, 24 vdc

0-100%

.08 mA

J3

7,8,9

Outdoor Humidity

ORH

4-20 mA,

Loop Powered

Option

4-20 mA, 24 vdc

0-100%

.08 mA

J3

10,11,1

2

Indoor CO

2

IAQ

4-20 mA,

Ext Sourced

Option

4-20 mA, 24 vdc

0-200 PPM/10

10 PPM

J3

13,14

Remote Minimum
Position Pot

MIN

10K

Option

10K to 100K Ohms

0 to 100%

1%

J3

15,16,1

7

RELAY OUTPUTS
Cooling Stage 1

CP1

Relay

Standard

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

1,3,4

Cooling Stage 2

CP2

Relay

Option

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

2,3,4

Power Exhaust 2/
Cooling Stage 3*

CP3/

EX2

Relay

Option

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

5,6

Power Exhaust 1/
Cooling Stage 4†

CP4/

EX1

Relay

Option

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

5,7

DISPLAY
Setpoint Switch 1

SP1

Digital

Standard

Open/Closed

Logic

Open/Closed

On Board

NA

Setpoint Switch 2

SP2

Digital

Standard

Open/Closed

Logic

Open/Closed

On Board

NA

LED 1

DS1

LED Output

Standard

Red

Logic

On/Off

On Board

NA

LED 2

DS2

LED Output

Standard

Yellow

Logic

On/Off

On Board

NA

LED 3

DS3

LED Output

Standard

Green

Logic

On/Off

On Board

NA

LED 4

DS4

LED Output

Standard

Green

Logic

On/Off

On Board

NA

Y1

Y2

G

OCC

24V

1

J1

5

Y1 (cool 1)

Y2 (cool 2)

G (fan)

OCC

24 VAC

THERMOST

A

T

INPUTS

Occupied/unoccupied
I/O support dry circuit
contact (min 24 mA I)

POWER

SUPPLY

2-10 VDC

ECONOMIZER

CONTROL

J2

1

5

CNT

24V

24V

24

V

A

C

24

V

A

C

Control

SA

T

OA

T

RA

T

IRH

VRF

ORH

VRF

IAQ

MIN

VRF

IAQ

(4-20ma)

min

(10K

pot)

ORH

(4-20

ma)

V

ref

V

ref

V

ref

IRH

(4-20

ma)

RA

T

(10k

thermistor)

OA

T

(10k

thermistor)

SA

T

(10k

thermistor)

J3

1

17

ANALOG INPUTS

4-20 mA external powered between signal and ground
4-20 mA loop powered between 24 VDC and signal

Relays rated at 24 VAC 3A
and traces for 8A.
NOTE: For 1 and 2 stage
cooling, 2 stages of power
exhaust will be used.
For 3 cooling stages, only 1
stage of power exhaust will be
used, and for 4 stages no power
exhaust will be controlled
directly by the control.

OUTPUT

RELA

YS

C1

C2

24V

24V

24V

C3

C4

24 VAC

24 VAC

24 VAC

CP1

CP2

EX2/CP3

EX1/CP4

J4

READ/

ADJUST

ADVANCE

MANUAL

DS1

DS2

SETPOINT DISPLAY

DS3

DS4

date or serial no

RED YELLOW

GREEN

PUSH BUTTONS

# 1

# 2

Fig. 36 — EconoMi$er+ Controller Board