Table 1 — physical data (cont) – Bryant DuraPac Series 580f User Manual

Page 9

Advertising
background image

9

Table 1 — Physical Data (cont)

LEGEND

*Evaporator coil fin material/condenser coil fin material. Contact your local rep-

resentative for details about coated fins.

†Weight of 14-in. roof curb.

**Single phase/three-phase.

††Rollout switch lockout is manually reset by interrupting power to unit or reset-

ting thermostat.

||California rated three-phase high heat models.

***Three phase standard high-heat models have heating input values as shown.

Single phase standard high heat models have one-stage heating with heating
input values as follows:
580FJV036115 — 115,000 Btuh
580FJV048150 — 150,000 Btuh
580FJV060150 — 150,000 Btuh

†††California SCAQMD compliant Low NO

x

models have combustion products

that are controlled to 40 nanograms per joule or less.

UNIT SIZE 580F

036

048

060

072 AND 073

FURNACE SECTION

Rollout Switch Cutout
Temp (F)††

195

195

195

195

Burner Orifice Diameter
(in. ...drill size)

Natural Gas

Std

074

.113...33

.113...33

.113...33

.113...33

114/115

.113...33

.113...33

.113...33

.113...33

149/150

.129...30

.129...30

.129...30

060N

.102...38

.102...38

.102...38

090N

.102...38

.102...38

.102...38

120N

.116...32

.116...32

Liquid Propane

Alt

074

.089...43

.089...43

.089...43

.089...43

114/115

.089...43

.089...43

.089...43

.089...43

149/150

.104...37

.104...37

.104...37

060N

.082...45

.082...45

.082...45

090N

.082...45

.082...45

.082...45

120N

.094...42

.094...42

Thermostat Heat Anticipator
Setting (amps)

208/230 v and 575

Stage 1

.14

.14

.14

.14

Stage 2

.14

.14

.14

.14

460 v

Stage 1

.14

.14

.14

.14

Stage 2

.14

.14

.14

.14

Gas Input (Btuh)

CA High Output 3-Phase Units

114||

115,000

149||

150,000

150,000

Standard Units

074

74,000/—

74,000/—

74,000/—

74,000/—

(Stage 2/ Stage 1)

115***

115,000/82,000

115,000/—

115,000/—

115,000/—

150***

150,000/120,000

150,000/120,000

150,000/120,000

Low NOx Units

060N†††

60,000

60,000

60,000

090N†††

90,000

90,000

90,000

120N†††

120,000

120,000

Efficiency (Steady

State) (%)

80

80

80

80

Temperature Rise Range

074

25-55

25-55

25-55

25-55

114/115

55-85

35-65

35-65

35-65

149/150

50-80

50-80

50-80

060N

20-50

20-50

20-50

090N

30-60

30-60

30-60

120N

40-70

40-70

Manifold Pressure (in. wg)

Natural Gas

Std

3.5

3.5

3.5

3.5

Liquid Propane

Alt

3.5

3.5

3.5

3.5

Gas Valve Quantity

1

1

1

1

Gas Valve Pressure Range

Psig

0.180-0.487

0.180-0.487

0.180-0.487

0.180-0.487

in. wg

5.0-13.5

5.0-13.5

5.0-13.5

5.0-13.5

Field Gas Connection
Size (in.)

1

/

2

1

/

2

1

/

2

1

/

2

HIGH-PRESSURE SWITCH (psig)

Standard Compressor

450 ± 50

500 ± 50

Internal Relief (Differential)
Cutout

428

428

Reset (Auto.)

320

320

LOSS-OF-CHARGE (LOW-PRESSURE SWITCH) (psig)

Cutout

7 ± 3

Reset (Auto.)

22 ± 7

FREEZE PROTECTION
THERMOSTAT (F)

Opens

30 ± 5

Closes

45 ± 5

OUTDOOR-AIR INLET SCREENS

Cleanable. Screen size and quantity varies with option selected.

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

Al

Aluminum

Bhp —

Brake Horsepower

Cu

Copper

Advertising