Table 31 — Fan Performance 580F060 — Horizontal Discharge Units, High-Static Motor (Belt Drive)*

LEGEND

*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied

drive.

NOTES:

1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 36 for general fan performance notes.

Table 32 — Fan Performance 580F072,073 — Horizontal Discharge Units, Standard Motor (Belt Drive)*

LEGEND

*Motor drive range: 1070 to 1460 rpm. All other rpms require a field-supplied

drive.

NOTES:

1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 36 for general fan performance notes.

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

790

0.40

353

896

0.53

470

990

0.67

599

1074

0.83

738

1151

1.00

886

1600

828

0.46

413

930

0.60

535

1021

0.75

669

1103

0.91

812

1179

1.09

965

1700

866

0.54

479

964

0.68

607

1053

0.84

746

1133

1.01

894

1207

1.18

1051

1800

905

0.62

553

1000

0.77

687

1085

0.94

831

1164

1.11

984

1236

1.29

1146

1900

944

0.71

635

1036

0.87

775

1119

1.04

924

1195

1.22

1082

1266

1.41

1248

2000

984

0.82

725

1072

0.98

871

1153

1.15

1025

1227

1.34

1189

1297

1.53

1360

2100

1024

0.93

824

1109

1.10

976

1188

1.28

1136

1260

1.47

1305

1328

1.67

1481

2200

1064

1.05

932

1147

1.23

1090

1223

1.41

1256

1294

1.61

1430

1360

1.81

1612

2300

1105

1.18

1050

1185

1.37

1215

1259

1.56

1386

1328

1.76

1566

1393

1.97

1752

2400

1146

1.33

1179

1223

1.52

1349

1295

1.72

1527

1362

1.93

1711

1426

2.14

1903

2500

1187

1.48

1317

1262

1.68

1494

1332

1.89

1677

1398

2.10

1868

1460

2.33

2065

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

1223

1.18

1045

1291

1.36

1212

1355

1.56

1388

1415

1.77

1573

1473

1.99

1765

1600

1249

1.27

1127

1316

1.46

1298

1379

1.66

1478

1439

1.87

1665

1496

2.09

1860

1700

1277

1.37

1217

1342

1.57

1392

1404

1.77

1575

1463

1.99

1766

1520

2.21

1965

1800

1305

1.48

1316

1369

1.68

1495

1430

1.89

1681

1489

2.11

1876

1545

2.34

2078

1900

1333

1.60

1423

1397

1.81

1606

1457

2.02

1797

1514

2.25

1995

1570

2.48

2200

2000

1363

1.73

1540

1425

1.94

1727

1484

2.16

1922

1541

2.39

2124

1596

2.63

2333

2100

1393

1.87

1665

1454

2.09

1857

1512

2.31

2056

1568

2.55

2262

1622

2.79

2475

2200

1424

2.03

1801

1484

2.25

1997

1541

2.48

2200

1596

2.71

2411

2300

1455

2.19

1946

1514

2.42

2147

1571

2.65

2355

1625

2.89

2570

2400

1487

2.37

2103

1545

2.60

2308

1601

2.84

2521

2500

1520

2.56

2269

1577

2.79

2480

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

919

0.63

561

1010

0.75

663

1095

0.87

771

1174

1.00

886

1250

1.14

1008

1900

960

0.73

648

1047

0.85

754

1129

0.98

867

1206

1.11

986

1279

1.25

1111

2000

1001

0.84

744

1085

0.96

855

1163

1.09

972

1238

1.23

1095

1309

1.38

1224

2100

1043

0.96

850

1123

1.09

965

1199

1.22

1086

1271

1.37

1213

1340

1.52

1346

2200

1085

1.09

966

1162

1.22

1086

1235

1.36

1211

1305

1.51

1342

1372

1.67

1479

2300

1127

1.23

1092

1201

1.37

1217

1272

1.52

1347

1340

1.67

1482

1405

1.83

1623

2400

1169

1.38

1229

1241

1.53

1359

1310

1.68

1493

1375

1.84

1633

1439

2.00

1778

2500

1212

1.55

1378

1281

1.70

1513

1348

1.86

1652

1412

2.02

1796

1473

2.19

1945

2600

1255

1.73

1539

1322

1.89

1678

1386

2.05

1822

1448

2.22

1970

1508

2.39

2124

2700

1298

1.93

1713

1363

2.09

1857

1425

2.26

2005

2800

1341

2.14

1899

1404

2.31

2048

2900

1384

2.36

2099

3000

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

1321

1.28

1137

1390

1.43

1273

1455

1.59

1415

1518

1.76

1563

1579

1.93

1718

1900

1348

1.40

1243

1415

1.56

1381

1479

1.72

1526

1541

1.89

1677

1601

2.06

1834

2000

1377

1.53

1359

1442

1.69

1500

1505

1.86

1648

1565

2.03

1801

1624

2.21

1961

2100

1406

1.67

1485

1470

1.83

1629

1531

2.00

1780

1591

2.18

1936

1648

2.36

2098

2200

1437

1.83

1621

1499

1.99

1769

1559

2.16

1923

1617

2.34

2082

2300

1468

1.99

1769

1529

2.16

1920

1587

2.34

2077

2400

1500

2.17

1928

1559

2.35

2083

2500

1533

2.36

2098

2600

2700

2800

2900

3000

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor

Advertising