Curbs & weights dimensions -- chassis 1, Table 7 – base unit dimensions -- chassis 1 – Bryant LEGACY 558J User Manual

Page 16

Advertising
background image

16

CURBS & WEIGHTS DIMENSIONS -- CHASSIS 1

Corner

D

Corner

A

Corner

B

Corner

C

6 1/8”

7”

10 1/2”

19 1/2”

22”

16 1/4”

11 3/8”

C08001

21 1/4”

19 1/2”

33 3/8”

16”

74 3/8”

J

4 5/8”

K

6 5/8”

C08000

Table 7 – BASE UNIT DIMENSIONS -- CHASSIS 1

UNIT

OPERATING

WGT (LB)

SHIPPING

WGT (LB)

J

CORNER WEIGHTS (LB)

CENTER OF GRAVITY (IN)

A

B

C

D

X

Y

HEIGHT

04

438

475

33 5/16”

108

115

110

104

38

23

17 1/4

05

494

530

33 5/16”

122

130

125

117

38

23

17 1/2

06

524

560

33 5/16”

130

138

132

124

38

23

17 3/4

07

607

645

41 5/16”

150

160

153

144

38

23

20 3/4

NOTES:

1. If one side has at least 36” (914mm) of clearance, the

opposite side can be reduced to 12” (305mm). Make

sure to plan for OA handler, if equipped.

2. Clearance of 0” requires use of an alternate drain con-

nection.

3. Maintain 36” (914mm) between control box and groun-

ded surface or 42” (1067mm) between control box and

ungrounded surfaces (concrete or block wall).

4. Keep combustible material at 36” (914mm) away from

the flue discharge. Accessory flue discharge deflector

may allow smaller clearance.

5. Units shown with optional economizer.
6. Local codes and jurisdictions may prevail.
7. Height is measured from bottom of base rail.

558J