Table 37 – mca/mocp determination w/ pwrd c.o – Bryant LEGACY 558J User Manual

Page 41

Advertising
background image

41

Table 37 – MCA/MOCP DETERMINATION W/ PWRD C.O.

UN

IT

V

---

P

H

---

H

Z

IFM

TYPE

ELECTRIC HEATER

w/ PWRD C.O.

kW

FLA

NO P.E.

w/ P.E. (pwrd fr/unit)

MCA

MOCP

DISC. SIZE

MCA

MOCP

DISC. SIZE

FLA

LRA

FLA

LRA

558J

*0

5

208/

230

---

1

---

60

STD

---

---

44.0

60

43

155

45.9

60

45

157

4.9/6.5

23.5/27.1

44.0/46.0

60/60

43/43

155/155

45.9/48.4

60/60

45/45

157/157

6.5/8.7

31.4/36.3

51.4/57.5

60/60

47/53

155/155

53.8/59.9

60/60

49/55

157/157

9.8/13.0

46.9/54.2

70.8/79.9

80/80

65/73

155/155

73.1/82.3

80/90

67/76

157/157

13.1/17.4

62.8/72.5

90.6/102.8

100/110

83/95

155/155

93.0/105.1

100/110

86/97

157/157

15.8/21.0

75.8/87.5

106.9/121.5

110/125

98/112

155/155

109.3/123.9

110/125

101/114

157/157

MED

---

---

46.1

60

45

180

48.0

60

48

182

4.9/6.5

23.5/27.1

46.1/48.6

60/60

45/45

180/180

48.0/51.0

60/60

48/48

182/182

6.5/8.7

31.4/36.3

54.0/60.1

60/70

50/55

180/180

56.4/62.5

60/70

52/58

182/182

9.8/13.0

46.9/54.2

73.4/82.5

80/90

68/76

180/180

75.8/84.9

80/90

70/78

182/182

13.1/17.4

62.8/72.5

93.3/105.4

100/110

86/97

180/180

95.6/107.8

100/110

88/99

182/182

15.8/21.0

75.8/87.5

109.5/124.1

110/125

101/114

180/180

111.9/126.5

125/150

103/116

182/182

208/

230

---

3

---

60

STD

---

---

30.7

45

31

131

32.6

45

33

133

4.9/6.5

13.6/15.6

30.7/31.6

45/45

31/31

131/131

32.6/34.0

45/45

33/33

133/133

7.9/10.5

21.9/25.3

39.5/43.8

45/45

36/40

131/131

41.9/46.1

45/50

39/42

133/133

12.0/16.0

33.4/38.5

53.9/60.3

60/70

50/55

131/131

56.3/62.6

60/70

52/58

133/133

15.8/21.0

43.8/50.5

66.9/75.3

70/80

62/69

131/131

69.3/77.6

70/80

64/71

133/133

19.9/26.5

55.2/63.8

81.1/91.9

90/100

75/85

131/131

83.5/94.3

90/100

77/87

133/133

MED

---

---

31.0

45

31

149

32.9

45

33

151

4.9/6.5

13.6/15.6

31.0/32.0

45/45

31/31

149/149

32.9/34.4

45/45

33/33

151/151

7.9/10.5

21.9/25.3

39.9/44.1

45/45

37/41

149/149

42.3/46.5

45/50

39/43

151/151

12.0/16.0

33.4/38.5

54.3/60.6

60/70

50/56

149/149

56.6/63.0

60/70

52/58

151/151

15.8/21.0

43.8/50.5

67.3/75.6

70/80

62/70

149/149

69.6/78.0

70/80

64/72

151/151

19.9/26.5

55.2/63.8

81.5/92.3

90/100

75/85

149/149

83.9/94.6

90/100

77/87

151/151

HIGH

---

---

33.3

45

34

175

35.2

50

36

177

4.9/6.5

13.6/15.6

33.3/34.9

45/45

34/34

175/175

35.2/37.3

50/50

36/36

177/177

7.9/10.5

21.9/25.3

42.8/47.0

45/50

39/43

175/175

45.1/49.4

50/50

42/45

177/177

12.0/16.0

33.4/38.5

57.1/63.5

60/70

53/58

175/175

59.5/65.9

60/70

55/61

177/177

15.8/21.0

43.8/50.5

70.1/78.5

80/80

65/72

175/175

72.5/80.9

80/90

67/74

177/177

19.9/26.5

55.2/63.8

84.4/95.1

90/100

78/88

175/175

86.8/97.5

90/100

80/90

177/177

46

0

---

3

---

60

STD

---

---

14.7

20

15

62

15.7

20

16

63

6.0

7.2

14.7

20

15

62

15.7

20

16

63

11.5

13.8

22.6

25

21

62

23.9

25

22

63

14.0

16.8

26.4

30

24

62

27.6

30

25

63

23.0

27.7

40.0

45

37

62

41.3

45

38

63

25.5

30.7

43.8

45

40

62

45.0

50

41

63

MED

---

---

15.2

20

15

71

16.2

20

16

72

6.0

7.2

15.2

20

15

71

16.3

20

16

72

11.5

13.8

23.3

25

21

71

24.5

25

23

72

14.0

16.8

27.0

30

25

71

28.3

30

26

72

23.0

27.7

40.6

45

37

71

41.9

45

39

72

25.5

30.7

44.4

45

41

71

45.6

50

42

72

HIGH

---

---

16.0

20

16

84

17.0

20

17

85

6.0

7.2

16.0

20

16

84

17.3

20

17

85

11.5

13.8

24.3

25

22

84

25.5

30

23

85

14.0

16.8

28.0

30

26

84

29.3

30

27

85

23.0

27.7

41.6

45

38

84

42.9

45

39

85

25.5

30.7

45.4

50

42

84

46.6

50

43

85

57

5

---

3

---

60

STD

---

---

11.5

15

12

48

13.4

15

14

50

MED

---

---

12.4

15

13

65

14.3

20

15

67

HIGH

---

---

12.4

15

13

65

14.3

20

15

67

LEGEND:

CO

--- Convenient outlet

DISC

--- Disconnect

FLA

--- Full load amps

IFM

--- Indoor fan motor

LRA

--- Locked rotor amps

MCA

--- Minimum circuit amps

MOCP

--- Maximum over current protection

PE

--- Power exhaust

UNPWRD CO

--- Unpowered convenient outlet

NOTES:

1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the

overcurrent protective device for the unit shall be fuse or HACR

breaker. Canadian units may be fuse or circuit breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage

is greater than 2%. Use the following formula to determine the

percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v

Maximum deviation is 4 v.

(BC) 231 – 227 = 4 v

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum

allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-

tact your local electric utility company immediately.

558J