Table 12 – STATIC PRESSURE ADDERS (Factory Options and/or Accessories)

CFM

600

800

1000

1250

1500

1750

2000

2250

2500

2750

3000

Vertical Economizer

0.01

0.02

0.035

0.045

0.065

0.08

0.12

0.145

0.175

0.22

0.255

Horizontal Economizer

---

---

---

---

---

0.1

0.125

0.15

0.18

0.225

0.275

CFM

600

900

1200

1400

1600

1800

2000

2200

2400

2600

1 Electric Heater Module

0.03

0.05

0.07

0.09

0.09

0.1

0.11

0.11

0.12

0.13

2 Electric Heater Modules

0.14

0.15

0.16

0.16

0.16

0.17

0.17

0.17

0.18

0.18

General fan performance notes:

1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static

pressure caused by any FIOPs or accessories.

3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories

may add static pressure losses, as shown in Table 12. Selection software is available, through your salesperson, to help

you select the best motor/drive combination for your application.

4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would

work, Bryant recommended the lower horsepower option.

5. For information on the electrical properties of Bryant’s motors, please see the Electrical information section of this

book.

6. For more information on the performance limits of Bryant’s motors, see the application data section of this book.