Table 34 – MCA/MOCP DETERMINATION W/ PWRD C.O.

UN

IT

V

---

P

H

---

H

Z

IFM

TYPE

ELECTRIC HEATER

NO C.O. or UNPWRD C.O.

kW

FLA

NO P.E.

w/ P.E. (pwrd fr/unit)

MCA

MOCP

DISC. SIZE

MCA

MOCP

DISC. SIZE

FLA

LRA

FLA

LRA

558J

*0

6

208/

230

---

1

---

60

STD

---

---

39.2

60

37

150

41.1

60

40

152

4.9/6.5

23.5/27.1

39.2/40.0

60/60

37/37

150/150

41.1/42.4

60/60

40/40

152/152

6.5/8.7

31.4/36.3

45.4/51.5

60/60

42/47

150/150

47.8/53.9

60/60

44/50

152/152

9.8/13.0

46.9/54.2

64.8/73.9

70/80

60/68

150/150

67.1/76.3

70/80

62/70

152/152

13.1/17.4

62.8/72.5

84.6/96.8

90/100

78/89

150/150

87.0/99.1

90/100

80/91

152/152

15.8/21.0

75.8/87.5

100.9/115.5

110/125

93/106

150/150

103.3/117.9

110/125

95/108

152/152

MED

---

---

41.3

60

40

175

43.2

60

42

177

4.9/6.5

23.5/27.1

41.3/42.6

60/60

40/40

175/175

43.2/45.0

60/60

42/42

177/177

6.5/8.7

31.4/36.3

48.0/54.1

60/60

44/50

175/175

50.4/56.5

60/60

46/52

177/177

9.8/13.0

46.9/54.2

67.4/76.5

70/80

62/70

175/175

69.8/78.9

70/80

64/73

177/177

13.1/17.4

62.8/72.5

87.3/99.4

90/100

80/91

175/175

89.6/101.8

90/110

82/94

177/177

15.8/21.0

75.8/87.5

103.5/118.1

110/125

95/109

175/175

105.9/120.5

110/125

97/111

177/177

208/

230

---

3

---

60

STD

---

---

25.9

30

25

126

27.8

40

27

128

4.9/6.5

13.6/15.6

25.9/25.9

30/30

25/25

126/126

27.8/28.0

40/40

27/27

128/128

7.9/10.5

21.9/25.3

33.5/37.8

40/40

31/35

126/126

35.9/40.1

40/45

33/37

128/128

12.0/16.0

33.4/38.5

47.9/54.3

50/60

44/50

126/126

50.3/56.6

60/60

46/52

128/128

15.8/21.0

43.8/50.5

60.9/69.3

70/70

56/64

126/126

63.3/71.6

70/80

58/66

128/128

19.9/26.5

55.2/63.8

75.1/85.9

80/90

69/79

126/126

77.5/88.3

80/90

71/81

128/128

MED

---

---

26.2

40

26

144

28.1

40

28

146

4.9/6.5

13.6/15.6

26.2/26.2

40/40

26/26

144/144

28.1/28.4

40/40

28/28

146/146

7.9/10.5

21.9/25.3

33.9/38.1

40/40

31/35

144/144

36.3/40.5

40/45

33/37

146/146

12.0/16.0

33.4/38.5

48.3/54.6

50/60

44/50

144/144

50.6/57.0

60/60

47/52

146/146

15.8/21.0

43.8/50.5

61.3/69.6

70/70

56/64

144/144

63.6/72.0

70/80

59/66

146/146

19.9/26.5

55.2/63.8

75.5/86.3

80/90

69/79

144/144

77.9/88.6

80/90

72/82

146/146

HIGH

---

---

28.5

40

28

170

30.4

45

30

172

4.9/6.5

13.6/15.6

28.5/28.9

40/40

28/28

170/170

30.4/31.3

45/45

30/30

172/172

7.9/10.5

21.9/25.3

36.8/41.0

40/45

34/38

170/170

39.1/43.4

45/45

36/40

172/172

12.0/16.0

33.4/38.5

51.1/57.5

60/60

47/53

170/170

53.5/59.9

60/60

49/55

172/172

15.8/21.0

43.8/50.5

64.1/72.5

70/80

59/67

170/170

66.5/74.9

70/80

61/69

172/172

19.9/26.5

55.2/63.8

78.4/89.1

80/90

72/82

170/170

80.8/91.5

90/100

74/84

172/172

46

0

---

3

---

60

STD

---

---

12.5

20

12

60

13.5

20

13

61

6.0

7.2

12.5

20

12

60

13.5

20

13

61

11.5

13.8

19.9

20

18

60

21.1

25

19

61

14.0

16.8

23.6

25

22

60

24.9

25

23

61

23.0

27.7

37.3

40

34

60

38.5

40

35

61

25.5

30.7

41.0

45

38

60

42.3

45

39

61

MED

---

---

13.0

20

13

69

14.0

20

14

70

6.0

7.2

13.0

20

13

69

14.0

20

14

70

11.5

13.8

20.5

25

19

69

21.8

25

20

70

14.0

16.8

24.3

25

22

69

25.5

30

23

70

23.0

27.7

37.9

40

35

69

39.1

40

36

70

25.5

30.7

41.6

45

38

69

42.9

45

39

70

HIGH

---

---

13.8

20

14

82

14.8

20

15

83

6.0

7.2

13.8

20

14

82

14.8

20

15

83

11.5

13.8

21.5

25

20

82

22.8

25

21

83

14.0

16.8

25.3

30

23

82

26.5

30

24

83

23.0

27.7

38.9

40

36

82

40.1

45

37

83

25.5

30.7

42.6

45

39

82

43.9

45

40

83

57

5

---

3

---

60

STD

---

---

9.8

15

10

46

11.7

15

12

48

MED

---

---

10.7

15

11

63

12.6

15

13

65

HIGH

---

---

10.7

15

11

63

12.6

15

13

65

LEGEND:

CO

--- Convenient outlet

DISC

--- Disconnect

FLA

--- Full load amps

IFM

--- Indoor fan motor

LRA

--- Locked rotor amps

MCA

--- Minimum circuit amps

MOCP

--- Maximum over current protection

PE

--- Power exhaust

UNPWRD CO

--- Unpowered convenient outlet

NOTES:

1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the

overcurrent protective device for the unit shall be fuse or HACR

breaker. Canadian units may be fuse or circuit breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage

is greater than 2%. Use the following formula to determine the

percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v

Maximum deviation is 4 v.

(BC) 231 – 227 = 4 v

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum

allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-

tact your local electric utility company immediately.

558J