Table 39 – mca/mocp determination w/ pwrd c.o – Bryant LEGACY 558J User Manual

Page 43

Advertising
background image

43

Table 39 – MCA/MOCP DETERMINATION W/ PWRD C.O.

UN

IT

V

---

P

H

---

H

Z

IFM

TYPE

ELECTRIC HEATER

w/ PWRD C.O.

kW

FLA

NO P.E.

w/ P.E. (pwrd fr/unit)

MCA

MOCP

DISC. SIZE

MCA

MOCP

DISC. SIZE

FLA

LRA

FLA

LRA

558J

*0

7

208/

230

---

1

---

60

STD

---

---

38.5

60

38

138

40.4

60

40

140

3.3/4.4

15.9/18.3

38.5/38.5

60/60

38/38

138/138

40.4/40.4

60/60

40/40

140/140

6.5/8.7

31.4/36.3

51.4/57.5

60/60

47/53

138/138

53.8/59.9

60/60

49/55

140/140

9.8/13.0

46.9/54.2

70.8/79.9

80/80

65/73

138/138

73.1/82.3

80/90

67/76

140/140

13.1/17.4

62.8/72.5

90.6/102.8

100/110

83/95

138/138

93.0/105.1

100/110

86/97

140/140

15.8/21.0

75.8/87.5

106.9/121.5

110/125

98/112

138/138

109.3/123.9

110/125

101/114

140/140

MED

---

---

38.5

60

38

138

40.4

60

40

140

3.3/4.4

15.9/18.3

38.5/38.5

60/60

38/38

138/138

40.4/40.4

60/60

40/40

140/140

6.5/8.7

31.4/36.3

51.4/57.5

60/60

47/53

138/138

53.8/59.9

60/60

49/55

140/140

9.8/13.0

46.9/54.2

70.8/79.9

80/80

65/73

138/138

73.1/82.3

80/90

67/76

140/140

13.1/17.4

62.8/72.5

90.6/102.8

100/110

83/95

138/138

93.0/105.1

100/110

86/97

140/140

15.8/21.0

75.8/87.5

106.9/121.5

110/125

98/112

138/138

109.3/123.9

110/125

101/114

140/140

208/

230

---

3

---

60

STD

---

---

28.3

40

29

104

30.2

40

31

106

4.9/6.5

13.6/15.6

29.1/31.6

40/40

29/29

104/104

31.5/34.0

40/40

31/31

106/106

6.5/8.7

18.1/20.9

34.8/38.3

40/40

32/35

104/104

37.1/40.6

40/45

34/37

106/106

12.0/16.0

33.4/38.5

53.9/60.3

60/70

50/55

104/104

56.3/62.6

60/70

52/58

106/106

15.8/21.0

43.8/50.5

66.9/75.3

70/80

62/69

104/104

69.3/77.6

70/80

64/71

106/106

MED

---

---

28.3

40

29

104

30.2

40

31

106

4.9/6.5

13.6/15.6

29.1/31.6

40/40

29/29

104/104

31.5/34.0

40/40

31/31

106/106

6.5/8.7

18.1/20.9

34.8/38.3

40/40

32/35

104/104

37.1/40.6

40/45

34/37

106/106

12.0/16.0

33.4/38.5

53.9/60.3

60/70

50/55

104/104

56.3/62.6

60/70

52/58

106/106

15.8/21.0

43.8/50.5

66.9/75.3

70/80

62/69

104/104

69.3/77.6

70/80

64/71

106/106

HIGH

---

---

28.6

40

29

122

30.5

40

31

124

4.9/6.5

13.6/15.6

29.5/32.0

40/40

29/29

122/122

31.9/34.4

40/40

31/32

124/124

6.5/8.7

18.1/20.9

35.1/38.6

40/40

32/36

122/122

37.5/41.0

40/45

35/38

124/124

12.0/16.0

33.4/38.5

54.3/60.6

60/70

50/56

122/122

56.6/63.0

60/70

52/58

124/124

15.8/21.0

43.8/50.5

67.3/75.6

70/80

62/70

122/122

69.6/78.0

70/80

64/72

124/124

46

0

---

3

---

60

STD

---

---

12.9

15

13

51

13.9

20

14

52

6.0

7.2

14.4

15

13

51

15.6

20

14

52

11.5

13.8

22.6

25

21

51

23.9

25

22

52

14.0

16.8

26.4

30

24

51

27.6

30

25

52

23.0

27.7

40.0

45

37

51

41.3

45

38

52

MED

---

---

12.9

15

13

51

13.9

20

14

52

6.0

7.2

14.4

15

13

51

15.6

20

14

52

11.5

13.8

22.6

25

21

51

23.9

25

22

52

14.0

16.8

26.4

30

24

51

27.6

30

25

52

23.0

27.7

40.0

45

37

51

41.3

45

38

52

HIGH

---

---

13.4

15

14

60

14.4

20

15

61

6.0

7.2

15.0

15

14

60

16.3

20

15

61

11.5

13.8

23.3

25

21

60

24.5

25

23

61

14.0

16.8

27.0

30

25

60

28.3

30

26

61

23.0

27.7

40.6

45

37

60

41.9

45

39

61

57

5

---

3

---

60

STD

---

---

9.0

15

9

46

10.9

15

11

48

MED

---

---

9.0

15

9

46

10.9

15

11

48

HIGH

---

---

9.1

15

9

52

11.0

15

12

54

LEGEND:

CO

--- Convenient outlet

DISC

--- Disconnect

FLA

--- Full load amps

IFM

--- Indoor fan motor

LRA

--- Locked rotor amps

MCA

--- Minimum circuit amps

MOCP

--- Maximum over current protection

PE

--- Power exhaust

UNPWRD CO

--- Unpowered convenient outlet

NOTES:

1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the

overcurrent protective device for the unit shall be fuse or HACR

breaker. Canadian units may be fuse or circuit breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage

is greater than 2%. Use the following formula to determine the

percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v

Maximum deviation is 4 v.

(BC) 231 – 227 = 4 v

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum

allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-

tact your local electric utility company immediately.

558J