Bryant LEGACY 558J User Manual

Page 36

Advertising
background image

36

Table 32 – MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.

UN

IT

V

---

P

H

---

H

Z

IFM

TYPE

ELECTRIC HEATER

NO C.O. or UNPWRD C.O.

kW

FLA

NO P.E.

w/ P.E. (pwrd fr/unit)

MCA

MOCP

DISC. SIZE

MCA

MOCP

DISC. SIZE

FLA

LRA

FLA

LRA

558J

*0

4

208/

230

---

1

---

60

STD

---

---

27.2

40

26

95

29.1

45

29

97

3.3/4.4

15.9/18.3

27.2/29.0

40/40

26/27

95/95

29.1/31.4

45/45

29/29

97/97

4.9/6.5

23.5/27.1

35.5/40.0

40/45

33/37

95/95

37.9/42.4

45/45

35/39

97/97

6.5/8.7

31.4/36.3

45.4/51.5

50/60

42/47

95/95

47.8/53.9

50/60

44/50

97/97

7.9/10.5

37.9/43.8

53.5/60.9

60/70

49/56

95/95

55.9/63.3

60/70

51/58

97/97

9.8/13.0

46.9/54.2

64.8/73.9

70/80

60/68

95/95

67.1/76.3

70/80

62/70

97/97

MED

---

---

27.2

40

26

95

29.1

45

29

97

3.3/4.4

15.9/18.3

27.2/29.0

40/40

26/27

95/95

29.1/31.4

45/45

29/29

97/97

4.9/6.5

23.5/27.1

35.5/40.0

40/45

33/37

95/95

37.9/42.4

45/45

35/39

97/97

6.5/8.7

31.4/36.3

45.4/51.5

50/60

42/47

95/95

47.8/53.9

50/60

44/50

97/97

7.9/10.5

37.9/43.8

53.5/60.9

60/70

49/56

95/95

55.9/63.3

60/70

51/58

97/97

9.8/13.0

46.9/54.2

64.8/73.9

70/80

60/68

95/95

67.1/76.3

70/80

62/70

97/97

208/

230

---

3

---

60

STD

---

---

19.4

25

19

89

21.3

30

22

91

3.3/4.4

9.2/10.6

19.4/19.4

25/25

19/19

89/89

21.3/21.8

30/30

22/22

91/91

4.9/6.5

13.6/15.6

23.1/25.6

25/30

21/24

89/89

25.5/28.0

30/30

23/26

91/91

6.5/8.7

18.1/20.9

28.8/32.3

30/35

26/30

89/89

31.1/34.6

35/35

29/32

91/91

7.9/10.5

21.9/25.3

33.5/37.8

35/40

31/35

89/89

35.9/40.1

40/45

33/37

91/91

12.0/16.0

33.4/38.5

47.9/54.3

50/60

44/50

89/89

50.3/56.6

60/60

46/52

91/91

MED

---

---

19.4

25

19

89

21.3

30

22

91

3.3/4.4

9.2/10.6

19.4/19.4

25/25

19/19

89/89

21.3/21.8

30/30

22/22

91/91

4.9/6.5

13.6/15.6

23.1/25.6

25/30

21/24

89/89

25.5/28.0

30/30

23/26

91/91

6.5/8.7

18.1/20.9

28.8/32.3

30/35

26/30

89/89

31.1/34.6

35/35

29/32

91/91

7.9/10.5

21.9/25.3

33.5/37.8

35/40

31/35

89/89

35.9/40.1

40/45

33/37

91/91

12.0/16.0

33.4/38.5

47.9/54.3

50/60

44/50

89/89

50.3/56.6

60/60

46/52

91/91

HIGH

---

---

19.7

30

20

107

21.6

30

22

109

3.3/4.4

9.2/10.6

19.7/19.8

30/30

20/20

107/107

21.6/22.1

30/30

22/22

109/109

4.9/6.5

13.6/15.6

23.5/26.0

30/30

22/24

107/107

25.9/28.4

30/30

24/26

109/109

6.5/8.7

18.1/20.9

29.1/32.6

30/35

27/30

107/107

31.5/35.0

35/40

29/32

109/109

7.9/10.5

21.9/25.3

33.9/38.1

35/40

31/35

107/107

36.3/40.5

40/45

33/37

109/109

12.0/16.0

33.4/38.5

48.3/54.6

50/60

44/50

107/107

50.6/57.0

60/60

47/52

109/109

46

0

---

3

---

60

STD

---

---

10.2

15

10

46

11.2

15

11

47

6.0

7.2

11.6

15

11

46

12.9

15

12

47

8.8

10.6

15.9

20

15

46

17.1

20

16

47

11.5

13.8

19.9

20

18

46

21.1

25

19

47

14.0

16.8

23.6

25

22

46

24.9

25

23

47

MED

---

---

10.2

15

10

46

11.2

15

11

47

6.0

7.2

11.6

15

11

46

12.9

15

12

47

8.8

10.6

15.9

20

15

46

17.1

20

16

47

11.5

13.8

19.9

20

18

46

21.1

25

19

47

14.0

16.8

23.6

25

22

46

24.9

25

23

47

HIGH

---

---

10.7

15

11

55

11.7

15

12

56

6.0

7.2

12.3

15

11

55

13.5

15

12

56

8.8

10.6

16.5

20

15

55

17.8

20

16

56

11.5

13.8

20.5

25

19

55

21.8

25

20

56

14.0

16.8

24.3

25

22

55

25.5

30

23

56

57

5

---

3

---

60

STD

---

---

7.3

15

7

44

9.2

15

9

46

MED

---

---

7.3

15

7

44

9.2

15

9

46

HIGH

---

---

7.4

15

7

50

9.3

15

10

52

LEGEND:

CO

--- Convenient outlet

DISC

--- Disconnect

FLA

--- Full load amps

IFM

--- Indoor fan motor

LRA

--- Locked rotor amps

MCA

--- Minimum circuit amps

MOCP

--- Maximum over current protection

PE

--- Power exhaust

UNPWRD CO

--- Unpowered convenient outlet

NOTES:

1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the

overcurrent protective device for the unit shall be fuse or HACR

breaker. Canadian units may be fuse or circuit breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage

is greater than 2%. Use the following formula to determine the

percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v

Maximum deviation is 4 v.

(BC) 231 – 227 = 4 v

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum

allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-

tact your local electric utility company immediately.

558J