Calibration – Hale AutoFill-E Tank Refill Control System User Manual

Page 41

Advertising
background image

Intelli-Tank Manual (106759) 021502

– 9 –

Class 1

The Intelli-Tank display can be calibrated three different ways: 2-point (level
calibration), 5-point and 9-point (volume calibration).

To enter calibration mode use a magnet and activate the magnetic switches in
the order of the appropriate password.

When a magnetic switch is activated the display will indicate which switch was activated
(Left = upper two LEDs, Right = lower two LEDs) for approximately half a second and
then the display will go blank. There is a limit of 2 seconds between switch activation’s
before the the unit reverts to normal operation.

Entering an invalid password will initiate a “wave off” pattern on the display. (Two center
LEDs, two outer LEDs flashing quickly for 4 cycles.)

Calibrate the unit by entering the desired point calibration –

2 point

RLLR LLRL

5 point

RLLR LRLR

9 point

RLLR RLLR