Troubleshooting – Hale AutoFill-E Tank Refill Control System User Manual

Page 55

Advertising
background image

Intelli-Tank Manual (106759) 12-15-03

– 9 –

Class 1

Condition

Evaluate

Bottom two lights

alternate flashing.

Master tank level display’s transducer signal voltage is below

.4VDC.
Check transducer wiring to master tank level display.

Top two lights

alternate flashing.

Master tank level display’s transducer signal voltage is above

4.80VDC.
Check transducer wiring to master tank level display.

Bottom two and

Upper two lights

alternate flashing.

Remote driver module is not receiving data from the master tank

level display.
Check for continuity on the data line (pin 10) to the master tank level

display and that the grounds are common between units (there

should be less than 1V difference of potential). Insure the master

tank level display is functioning properly.

Bottom and top

lights alternate

flashing (center two

are off)

Master tank level display has an invalid calibration.
Recalibrate Master display.

No lights are on.

Unit is not powered or external lights are not connected properly.
Check power (Stud) and ground (Pin 12) connection for proper

voltage.

Unit will not dim

lights.

Check for proper ground input signal to pin 6 when activating the

dim input switch.

Alarm will not

silence.

Check for proper ground input signal to pin 5 when activating the

alarm silence switch.

Auto fill not

functioning

Check for proper ground input signal to pin 8 when activating the

auto-fill select switch.
Insure remote driver is displaying same information as master tank

level display.