Warning, Control instrument parameter programming mode – Despatch LBB2-xxA/B-2 User Manual

Page 33

Advertising
background image

LBB Series Oven Owner’s Manual

O

PERATION

Version

18

33

5.4.2. Control Instrument Parameter Programming Mode

Warning!

Changing program parameters alters the function of the Control.
Proceed carefully and fully understand each parameter before
changing that parameter.

Control instrument parameters are set through the Operating and Set-up modes. In most
applications, it is not necessary to alter the oven settings. The following instructions describe how
to access, view and if desired, change the parameters. Once the Operating and Set-up modes are
accessed,

SP

will start blinking on and off. Table 4 and Table 5 explain the Operating and Set-up

Mode parameters.

The Control Instrument will not allow the display to be altered improperly. The Control
Instrument will automatically exit the Parameter Programming mode if no keys are pressed for
about two (2) minutes.

5.4.2.1. Entering Control Instrument Set-up and Configuration Mode

To enter the Operating and Set-up Mode (Figure 4):
1.

Press

for three (3) seconds.

2.

Press

until the desired parameter displays. See Table 4 for more information.

3.

Press ▲ or ▼ to display the value.

4.

Use ▲ or ▼ to move to the desired setting.

5.

Press

to enter the value.

6.

Press

and hold for three (3) seconds to return to the display mode.


Table 4. Control Instrument Set-up Parameters.

Code Name

Description

Settings

CtL

Control
Mode

Determines whether controller functions as a time
proportional or an on/off control.

PID

At

Auto-tuning

OFF for PID tuning, ON for controller to tune process

OFF

P

Proportional
Band

Expressed in degrees, value determines the band width
on both sides of the setpoint within which the control
provides proportional control.

4

(8 if

°°°°

F)

*

I

Integral
Time

Expressed in seconds, value corrects for errors in actual
temperature versus the setpoint

15

d

Derivative
Time

Expressed in seconds, value shows the effect of the
derivative time is in direct proportion to the time setting

0

Ct

Cycle Time

Expressed in seconds, value shows total time for one
ON/OFF cycle of the controller output during the
proportional action

1

FL

Input Filter

Expressed in seconds. Use this function when the PV may
fluctuate greatly (for example, when an input signal
contains noise)

0

Advertising