Danger, Warning – Despatch LBB2-xxA/B-2 User Manual

Page 37

Advertising
background image

LBB Series Oven Owner’s Manual

O

PERATION

Version

18

37

5.4.5. Set the High Limit

Danger!

Failure to heed warnings in this instruction manual and on the
oven could result in personal injury, property damage or death.

The oven has been factory-tested with the High Limit instrument factory-preset for normal
operating conditions. In most applications, it will not be necessary to alter the oven's settings,
except for the Setpoint. This section contains information and reference material to change
Setpoint, access the Set-up mode and change display between °C and °F.

The High Limit instrument was carefully programmed at the factory using the Operating and Set-
up mode. The parameters that may be accessed include; display functions, and thermocouple
selection.

5.4.5.1. Change the High Limit Instrument Setpoint

Warning!

Never operate oven at a temperature in excess of the maximum
operating temperature of 204°C (400°F).

Enter setpoint on the High Limit instrument. Set High Limit instrument to a temperature 10°C to
14°C higher than the setpoint or to a temperature that should not be exceeded in the process.
1.

If

on the High Limit instrument is lit, press and hold

for four (4) seconds to

enable and .

2.

Press

, HSP1 will light.

3.

Use and to set High Limit temperature.

4.

Press

or

once to return (also enters the value) to the process variable PV mode.

5.

If the High Limit instrument is exceeded the heater will shut down.

6.

Reset the High Limit instrument by pushing

on the High Limit instrument.


5.4.6. High Limit Instrument Parameter Setup Mode

Warning!

Changing program parameters alters the function of the High
Limit. Proceed carefully and fully understand each parameter
before changing that parameter.