Figure 7—ex d wiring option, Figure 8—ex e wiring option – Det-Tronics X5200 UVIR Flame Detector User Manual

Page 12

Advertising
background image

95-8546

10

13.1

B2136

FIRE ALARM PANEL

X5200 DETECTOR

ALARM

24 VDC

+

WIRING NOTES:

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND

THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.

2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3 INDIVIDUAL MANUAL

oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND

ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.

4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION

FOR INSTALLATION DETAILS.

E.O.L.

DEVICE4

oi TEST 3

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

COM FIRE2

COM FIRE

N.O. FIRE2

N.O. FIRE

N.C. FIRE2

N.C. FIRE

COM FAULT1

COM FAULT

N.O. FAULT1

N.O. FAULT

24 VDC +

24 VDC +

24 VDC –

24 VDC –

24 VDC –

29

28

27

26

25

24

23

22

21

SPARE

SPARE

RS-485 A

RS-485 B

MAN

Oi

4-20 mA +

4-20 mA –

4-20 mA + REF

4-20 mA – REF

COM AUX

N.O. AUX

N.C. AUX

figure 7—Ex d Wiring Option

B2137

FIRE ALARM PANEL

X5200 DETECTOR

ALARM

ALARM

24 VDC

+

WIRING NOTES:

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND

THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.

2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3 INDIVIDUAL MANUAL

oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND

ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.

4 EOL RESISTOR SUPPLIED BY PANEL.

EOL

DEVICE 4

oi TEST 3

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

COM FIRE2

COM FIRE

N.O. FIRE2

N.O. FIRE

N.C. FIRE2

N.C. FIRE

COM FAULT1

COM FAULT

N.O. FAULT1

N.O. FAULT

24 VDC +

24 VDC +

24 VDC –

24 VDC –

24 VDC –

29

28

27

26

25

24

23

22

21

SPARE

SPARE

RS-485 A

RS-485 B

MAN

Oi

4-20 mA +

4-20 mA –

4-20 mA + REF

4-20 mA – REF

COM AUX

N.O. AUX

N.C. AUX

figure 8—Ex e Wiring Option