Specifications – Det-Tronics X5200 UVIR Flame Detector User Manual

Page 20

Advertising
background image

95-8546

18

13.1

SPECIfICaTIONS

OPERaTINg VOLTagE—

24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).

Maximum ripple is 2 volts peak-to-peak.

POWER CONSUmPTION—

Without heater: 2.8 watts at 24 Vdc nominal;

4.8 watts at 24 Vdc in alarm.

3.1 watts at 30 Vdc nominal;

5.4 watts at 30 Vdc in alarm.

Heater only: 8 watts maximum.

Total power:

17.5 watts at 30 Vdc with EOL resistor

installed and heater on maximum.

EOL resistor must be ceramic, wirewound type, rated

5 watts minimum, with actual power dissipation not to

exceed 2.5 watts.

For HART models, refer to Addendum number 95-8636.

POWER UP TImE—

Fault indication clears after 0.5 second; device is ready

to indicate an alarm condition after 30 seconds.

OUTPUT RELayS—

Fire Alarm relay, Form C, 5 amperes at 30 Vdc:

The Fire Alarm relay has redundant terminals

and normally open / normally closed contacts,

normally de-energized operation, and latching or

non-latching operation.

Fault relay, Form A, 5 amperes at 30 Vdc:

The Fault relay has redundant terminals and

normally open contacts, normally energized

operation, and latching or non-latching operation.

Auxiliary relay, Form C, 5 amperes at 30 Vdc:

The auxiliary relay has normally open / normally

closed contacts, nor mally energized or

de-energized operation, and latching or non-

latching operation.

CURRENT OUTPUT (Optional)—

0 to 20 milliampere (±0.3 mA) dc current, with a

maximum loop resistance of 500 ohms from 18 to

19.9 Vdc and 600 ohms from 20 to 30 Vdc.

LON OUTPUT—

Digital communication, transformer isolated (78.5 kbps).

TEmPERaTURE RaNgE—

Operating: –40°F to +167°F (–40°C to +75°C).

Storage:

–67°F to +185°F (–55°C to +85°C).

Hazardous location ratings from –55°C to +75°C available

on flameproof model.

hUmIDITy RaNgE—

0 to 95% relative humidity, can withstand 100%

condensing humidity for short periods of time.

0°

15°

30°

45°

15°

30°

45°

VIEWING ANGLE

B1288

100 ft (30.5 m)

90 ft (27.4 m)

80 ft (24.4 m)

70 ft (21.3 m)

60 ft (18.3 m)

50 ft (15.2 m)

40 ft (12.2 m)

30 ft 9.1 m)

20 ft (6.1 m)

10 ft (3 m)

DETECTION

DISTANCE

(PERCENT)

100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A

GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF

INCIDENCE DECREASES.

figure 19—Detector Cone of Vision

10.2

(25.9)

4.8

(12.2)

4.7

(11.9)

B2223

figure 20—Dimensions in Inches (cm)