Instructions uvir flame detector x5200 – Det-Tronics X5200 UVIR Flame Detector User Manual

Page 3

Advertising
background image

1

95-8546

13.1

Important

Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.

attEntIon

The X5200 includes the Automatic

oi ®

(Optical

Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
testing with an external test lamp is not
approved or required
.

DESCRIPTION

The X5200 UVIR Flame Detector meets the most

stringent requirements worldwide with advanced

detection capabilities and immunity to extraneous

sources, combined with a superior mechanical design.

The mounting arrangement allows the UV and IR sensors

to monitor the same hazardous location with a 90 degree

cone of vision. When both sensors simultaneously detect

the presence of a flame, an alarm signal is generated.

The detector has Division and Zone explosion-proof

ratings and is suitable for use in indoor and outdoor

applications.

The standard output configuration includes fire, fault and

auxiliary relays. Output options include:

0 to 20 mA output (in addition to the three relays)

Pulse output for compatibility with existing Detector

Electronics Corporation (Det-Tronics

®

) controller

based systems (with fire and fault relays)

Eagle Quantum Premier

®

(EQP) compatible model

(no analog or relay outputs)

HART communication

A tri-color LED on the detector faceplate indicates

normal condition and notifies personnel of fire alarm or

fault conditions.

Microprocessor controlled heated optics increase

resistance to moisture and ice.

The X5200 housing is available in copper-free aluminum

or stainless steel, with NEMA/Type 4X and IP66/IP67

rating.

OuTpuTs
Relays
The standard detector is furnished with fire, fault and

auxiliary relays. All three relays are rated 5 amperes at

30 Vdc.

The Fire Alarm relay has redundant terminals and

normally open / normally closed contacts, normally

de-energized operation, and latching or non-latching

operation.

The Fault relay has redundant terminals and normally

open contacts, normally energized operation, and

latching or non-latching operation.

INsTRuCTIONs

UVIR flame Detector

X5200

©

Detector Electronics Corporation 2013

Rev: 10/13